Further information for Dold 0058941 BA9019/100 3AC50/60HZ 200-480V 3KW soft starter
Technical data
Extra functions
Temperature monitoring
For three-phase motors, 400 V up to
5,5 kW
Load voltage up to
3AC 460 V
Width
45 mm
Type
BA 9019
Auxiliary voltage required
Variant
Mains / motor voltage
3AC 200 - 480 V
Nominal motor power
3 kW
Variant
Eceleration time from 0 ... 5 s adjustable
The Dold BA9019/100 is an electronic soft-start and soft-stop device for three-phase asynchronous motors, specifically designed for applications with motor powers up to 5.5 kW at 400 V supply voltage. The variant described here is designed for a rated power of 3 kW and operates in the voltage range of 3AC 200 V to 480 V at frequencies of 50/60 Hz. The device enables a jerk-free start and gentle braking of motors, thereby reducing mechanical stress on drive components such as gearboxes, belts or chains. The function is based on phase-angle control via alternistors, which influence two motor phases, allowing the current and torque to increase gradually. After start-up, the semiconductors are bypassed to minimize power losses in the device.
Applications
This device is suitable for industrial drives, particularly in machines with gearbox, belt or chain drives, as well as in conveyor belts, fans, pumps, compressors, woodworking machines, centrifuges, packaging machines and door drives. The gentle start and stop characteristics protect mechanical components and prevent damage caused by sudden load peaks. The application is especially beneficial for drives transporting sensitive materials or where an abrupt stop could cause mechanical stress.
Functions and Equipment in Detail
The BA9019/100 offers separate adjustment options for start-up and stop time, as well as for initial and stop torque. The start-up ramp is adjustable between 0.5 and 5 seconds, as is the stop ramp. The start-up voltage is between 50 and 80 %, and the stop voltage between 30 and 80 % of the rated voltage. The integrated temperature monitoring protects the device from overheating. Control is via a galvanically isolated DC control input (X1/X2), which starts the start-up when the voltage exceeds 13 V DC and triggers the stop when it falls below 5 V DC. The auxiliary voltage (A1/A2) is DC 24 V ± 20 % and is required for operation.
Technology Explained Simply
Control is achieved via electronic phase-angle control, where two motor phases are controlled via alternistors. This allows the current to be gradually increased, enabling a smooth rise in torque. This prevents jerks during start-up and reduces mechanical stress. After reaching nominal speed, the semiconductors are bypassed to minimize power losses. The soft-stop function extends the natural braking time to avoid abrupt stopping. The re-readiness time is 200 ms, which limits the switching frequency. The operating temperature ranges from 0 °C to +55 °C, and the storage temperature ranges from -25 °C to +75 °C.
Compatibility and Accessories
The device is designed for 3-phase motors and complies with the standard IEC/EN 60947-4-2. The width is 45 mm, allowing installation in standard control panels. The auxiliary voltage is required, and the supply is via DC 24 V. The connection terminals are clearly labeled: A1/A2 for auxiliary voltage, X1/X2 for control input, L1/L2/L3 for supply voltage, and T1/T2/T3 for motor connection. The integrated temperature monitoring activates a red LED when the temperature limit is reached. A green LED indicates that the auxiliary voltage is present, and a yellow LED blinks during ramp operation and remains lit when the semiconductors are bypassed.
Mounting and Installation
Mounting is done in standard control panels with a width of 45 mm. The connection terminals are clearly labeled and allow for secure connections. The auxiliary voltage (DC 24 V) must be connected, as well as the control input (X1/X2). The supply voltage (L1/L2/L3) and the motor (T1/T2/T3) are connected accordingly. The switching frequency is limited to avoid thermal stress. Protection is provided according to assignment type 1 (gG 32 A) or assignment type 2 (semiconductor fuse max. 610 A/2 s), depending on requirements.
Advantages in Operation
The device reduces mechanical stress in the drive, extending the service life of machine components. The gentle start and stop characteristics protect sensitive materials and prevent disruptions in production. The integrated temperature monitoring increases operational safety. The galvanic isolation between control input and auxiliary voltage enhances safety and prevents interference. The clear LED display allows for quick diagnosis of the operating status. The re-readiness time of 200 ms limits the switching frequency and protects the device from overload.