| Technical data |
| Load current up to | 125 A |
| Load voltage up to | AC 600 V |
| Number of poles | 1-pole |
| On/Off Input Control | AC/DC, DC |
| Width | 45 mm |
| Type | PH 9260 |
| Variant |
| Control voltage | DC 4 - 32 V |
| Load current | AC 25 A |
| Load voltage | AC 48 - 600 V |
| Semiconductor output | 1-pole |
| Variant | Switching at zero crossing. Without heat sink |
The Dold semiconductor relay PH9260.91 AC48-600V AC25A is an
AC semiconductor relay for use in industrial applications. It is designed for wear-free and noiseless switching of loads such as heaters, motors, valves, and lighting systems. The device is manufactured in accordance with the standard
IEC/EN 60947-4-3 and features a
single-pole semiconductor output with a load voltage of AC 48 to 600 V and a load current of AC 25 A. The control voltage is DC 4 to 32 V, enabling flexible connection to digital control systems. The width of 45 mm allows for compact mounting on standard DIN rail.
Applications
This relay is designed for use in machine building and automation technology, particularly in applications such as injection moulding machines, packaging machines, soldering systems, and food processing equipment. The zero-voltage switching function ensures a gentle switching process, extending the service life of both the load and the relay. The
zero-voltage switching function activates the output at the next zero crossing of the sinusoidal supply voltage as soon as the control voltage is applied. When the control voltage is removed, the relay switches off at the next zero crossing of the load current. This minimizes current surges and electromagnetic interference.
Functions and Equipment in Detail
The device is based on two antiparallel-connected thyristors that provide the switching function. The
DCB technology (Direct-Copper-Bonding process) ensures excellent heat transfer, increasing thermal load capacity. The
LED status indicator signals the state of the control input, enabling visual monitoring of operation. The terminals are designed as
box terminals, allowing for secure and easy connection. The
shock protection class IP20 protects against contact with moving parts and is suitable for use in enclosed enclosures.
Technology Explained Simply
The
peak blocking voltage is 1200 V or 1600 V, depending on the variant, and the
insulation voltage is 4000 V, ensuring high electrical safety. The device is designed for continuous operation and can switch loads up to 125 A (AC-51), with a maximum I²t value of 18000 A²s. This makes it suitable for applications with high thermal loads. The
thermal resistances are specified as 0.6 K/W (junction-to-case) and 12 K/W (case-to-ambient), describing the thermal performance.
Compatibility and Accessories
The relay is configured as
zero-voltage switching and is supplied without a heatsink. Optional variants with heatsinks for DIN rail mounting are available, enabling optimal heat dissipation. An
over-temperature protection can be optionally integrated by inserting a temperature-limit switch (normally open) into a designated slot on the underside. If the temperature exceeds the set limit (e.g. 100 °C), the switch opens and protects the device. The device is standardly designed for DIN rail mounting.
Mounting and Installation
Mounting is carried out on standard DIN rail (DIN rail) inside enclosures. The box terminals allow for easy and secure connection of wires. The terminal markings are clearly indicated: A1(+)/A2 for the control input, L1 for the supply connection, and T1 for the load output. The operating temperature range is from -20 °C to +40 °C, and the storage temperature range is from -20 °C to +80 °C. The mechanical endurance is specified according to IEC/EN 60068-2-6 with an amplitude of 0.35 mm and a frequency of 10 to 55 Hz.
Advantages in Operation
The relay offers wear-free operation, as it has no mechanical contacts. Switching operations are noiseless and allow for high switching frequencies. The
zero-voltage switching reduces current surges and electromagnetic interference, extending the service life of both the load and the relay. The
LED indicator simplifies diagnosis and maintenance. The
DCB technology ensures efficient heat dissipation, increasing thermal load capacity and reliability. Compliance with the standard IEC/EN 60947-4-3 ensures safety and reliability in industrial applications.