Further information for Dold 0058055 IL5991 AC/DC24V 3S fault indication extension
Technical data
Alarm inputs
4
Alarm inputs extendable up to
160
Enclosure design
Distribution board
Operating principle
De-energized on trip, Energized on trip
Optical signal
LED
Width
35 mm
Type
IL 5991
Optional buzzer
Variant
Contact equipping
2 x 1 NO contact
Nominal voltage
AC/DC 24 V
Operate delay
3 s
The Dold IL5991 AC/DC24V 3S is a fault alarm monitor from the INFOMASTER series, specifically designed for monitoring industrial plants and buildings. As an expansion device for the fault alarm system IL 5990/SL 5990, it enables the extension of the number of monitorable fault alarm inputs. The device features 4 fault alarm inputs, which can be switched between operating current principle (output relay is activated in case of fault) and rest current principle (output relay is not activated in case of fault) via bridges X1-X2. The response delay is standardly 3 seconds, with adjustment possible up to 10 seconds to avoid false alarms. The rated voltage is AC/DC 24 V, with the devices also suitable for AC 230 V. The width is 35 mm, and the device is delivered in I form, featuring a depth of 61 mm and bottom-mounted connection terminals for installation and industrial distributors according to DIN 43880.
Applications
This device is intended for integration into industrial monitoring systems, particularly in plants where central fault reporting is required. It is suitable for monitoring machines, drives, pumps, air conditioning systems, or other technical installations where signal loss or interruption of power supply must be detected as a fault. The scalability from 4 to 160 fault alarm inputs allows flexible expansion of the monitoring system according to requirements.
Functions and Equipment in Detail
Each of the four fault alarm inputs is equipped with an LED, enabling visual fault indication. The LED lights up when a fault is activated and remains on until acknowledged. The front-mounted acknowledge button QH is used for manual acknowledgment of the alarm and can also be used for an external alarm device. The output contacts consist of 2 x 1 normally open contact, with one contact designated for the collective alarm and one for the horn output. The contacts are rated for a thermal current of 5 A and can switch 1 A / AC 230 V according to AC 15. The electrical life is at least 150,000 switching operations at 1 A and AC 230 V.
Technology Explained Simply
The device operates on the operating current and rest current principle, with the setting adjusted via bridges X1-X2. In operating current mode, the output relay is activated when the circuit is interrupted (e.g., defective sensor). In rest current mode, the relay is activated only when the circuit is closed (e.g., short circuit). The response delay of 3 seconds prevents short-term, irrelevant faults. The terminals are designed for conductor cross-sections of 2 x 2.5 mm² solid or 2 x 1.5 mm² stranded wire with ferrule according to DIN 46228. Mounting is done via DIN rail according to IEC/EN 60715.
Compatibility and Accessories
The IL5991 is designed as an expansion device for the fault alarm system IL 5990/SL 5990. It can be combined with the alarm device IK/SK 8832 to generate an acoustic alarm. The bus lines H and S carry low voltage and must not be subjected to foreign voltages. In cases of inductive or capacitive interference from high-current lines, the use of shielded cables is recommended, with the shield connected to PE.
Mounting and Installation
Mounting is done on a DIN rail. Connections A1, S1–S4, and QH must be connected to the same phase. The normally open contacts 13–14 and 23–24 must also be connected to the same phase. The operating temperature range is between -20 °C and +60 °C, and the storage temperature range is between -25 °C and +60 °C. The operating altitude is limited to below 2000 m. The housing has protection rating IP 40 (housing) and IP 20 (terminals) according to IEC/EN 60529, providing protection against touch and dust, but not against water.
Operational Advantages
The expandability up to 160 inputs enables flexible system expansion. The adjustable response delay reduces false alarms. The LED display and the acknowledge button provide clear visual and manual feedback. The combination with external alarm devices extends alarm options. The device is designed for continuous operation and complies with standard DIN 19235.