Dold 0057884, EAN: 4030641578848

Dold 0057884 semiconductor contactor AC110-240V 10A

Dold 0057884 semiconductor contactor AC110-240V 10A

Lieske Part No. 1001497
Mfg Part No 0057884
EAN-Code 4030641578848
Manufacturer Dold
Here only 191,91 EUR
228,37 EUR incl. VAT

Further information for Dold 0057884 semiconductor contactor AC110-240V 10A

Technical data
Analog Input Control4 - 20 mA
ApprovalsUL
Load current up to50 A
Load voltage up toAC 480 V
Number of poles1-pole
Width22,5 mm, 45 mm, 90 mm
TypeBF 9250/0_2
Temperature monitoringYes
Variant
Auxiliary voltageAC/DC 24 V
Contact equippingwithout signal contact
Control inputremote poti 10 kOhm
Load currentAC 10 A
Load voltageAC 110 - 240 V
Semiconductor output1-pole
Approvals and MarkingsUL-listed C/US
VariantOutput control with fixed period of 64 cycles
The Dold semiconductor contactor BF9250.91/002 UH=AC/DC24V 10K is a 1-pole device for pulse packet control of heating elements in industrial applications. It enables precise temperature control through analog actuation and is designed for use in systems with AC/DC 24 V auxiliary voltage. Control is performed via a remote potentiometer with 10 kOhm, where the output power is distributed linearly in the form of pulse packets over 64 cycles. The device is zero-voltage switching, ensuring noiseless and disturbance-free switching operations, particularly with resistive loads such as heaters.

Applications
This contactor is designed for use in industrial heating systems where precise and disturbance-free temperature control is required. It is particularly suitable for applications requiring continuous, analog control of heating power, such as process heating, drying systems, or temperature control devices. The pulse packet control allows fine adjustment of power, achieving stable temperature regulation. The load voltage ranges from AC 110–240 V, with the device also rated for voltages up to AC 480 V. The load current is AC 10 A, with a width of 22.5 mm specified for this rated capacity.

Functions and Equipment in Detail
The device features an LED indicator that visually signals the operating status: the green LED indicates supply voltage, the yellow LED indicates output status, and the red LED indicates alarms. In the event of a synchronization error, a control input fault, or overtemperature of the power semiconductor, the red LED illuminates. The overtemperature alarm is latching and must be reset by briefly switching off the supply voltage. The temperature protection function for the power semiconductors protects the device from thermal overload. A varistor protection safeguards the semiconductors against overvoltage. Control is performed via an analog input, which can be operated as DC 0–10 V, DC 4–20 mA, or 0–10 kΩ (remote potentiometer). Inverted analog inputs are also possible.

Technology Explained Simply
The pulse packet control operates on the principle of zero-voltage switching, where the switch only operates at the zero-crossing point of the alternating voltage. This minimizes switching disturbances and extends the lifespan of the semiconductors. The linear distribution of pulses over 64 cycles ensures uniform and precise power regulation. The resolution of the output control is 1.5625 %, enabling fine adjustment of heating power. The control inputs are equipped with overcurrent and reverse polarity protection, with a voltage drop at the input of 1.02 V at 20 mA. The load voltage can reach up to AC 480 V, and the load current is available up to AC 50 A, with the width varying according to rated current (22.5 mm up to 10 A, 45 mm up to 25 A, 90 mm up to 50 A).

Compatibility and Accessories
The device is mountable on a DIN rail and complies with standards IEC/EN 60947-4-2 and IEC/EN 60947-4-3. It is UL-listed C/US, thus approved for use in the USA and Canada. The load type is designed for resistive loads, as commonly found in heaters. The frequency range is between 45 and 65 Hz. The blocking voltage is ±1200 V, and the varistor voltage is rated for AC 510 V. The power losses amount to approximately 1.2 V multiplied by the load current in amperes.

Mounting and Installation
The device is designed for mounting on a DIN rail. Recommended clearances to the surrounding environment are 20 mm above and below, and 10 mm to the left and right, to ensure sufficient cooling at maximum load current and 100 % duty cycle. The operating temperature ranges from 0 to 40 °C, with a maximum temperature of 60 °C possible under derating conditions. The maximum air humidity is 75 %, without condensation.

Operational Advantages
The semiconductor contactor offers noiseless switching, high service life due to zero-voltage switching, and precise temperature control via analog control. The integrated LED indicator enables quick fault diagnosis. The temperature protection function and varistor protection enhance reliability. The DIN rail mounting simplifies installation in enclosures. The 4–20 mA control input is standard in many industrial control systems, simplifying integration into existing installations.