Dold 0057700, EAN: 4030641577001

Dold 0057700 PH9260.91/100 AC48-480V AC50A semiconductor relay UH=DC4-32V

Dold 0057700 PH9260.91/100 AC48-480V AC50A semiconductor relay UH=DC4-32V

Lieske Part No. 1001372
Mfg Part No 0057700
EAN-Code 4030641577001
Manufacturer Dold
Here only 75,93 EUR
90,36 EUR incl. VAT

Further information for Dold 0057700 PH9260.91/100 AC48-480V AC50A semiconductor relay UH=DC4-32V

Technical data
Load current up to125 A
Load voltage up toAC 600 V
Number of poles1-pole
On/Off Input ControlAC/DC, DC
Width45 mm
TypePH 9260
Variant
Control voltageDC 4 - 32 V
Load currentAC 50 A
Load voltageAC 48 - 480 V
Semiconductor output1-pole
VariantSwitching at zero crossing. With heigh I2t-value. Without heat sink.
The Dold semiconductor relay PH9260.91/100 AC48-480V AC50A is a 1-pole AC semiconductor relay/contactors designed for use in industrial applications. It is used for wear-free and noiseless switching of loads such as heaters, motors, valves, and lighting systems. The device operates according to the standard IEC/EN 60947-4-3 and is standardly configured as zero-voltage switching, meaning the switching process occurs at the next zero crossing of the sinusoidal mains voltage. This minimizes electrical interference and extends the service life of connected devices. The control voltage is in the range DC 4–32 V, allowing flexible connection to digital control systems.

Applications
This semiconductor relay is suitable for applications in the plastics and rubber industry, packaging machines, soldering systems, and the food industry. It is particularly suitable for machines requiring frequent switching without mechanical contact wear. Zero-voltage switching ensures gentle load activation, which is advantageous for sensitive loads such as motors or heaters. Alternatively, a peak-voltage switching variant is available, specifically developed for switching transformers to avoid high inrush current.

Functions and Equipment in Detail
The device features two antiparallel-connected thyristors responsible for the switching function. The DCB technology (Direct-Copper-Bonding process) ensures excellent heat transfer, reducing thermal stress and increasing reliability. The LED status indicator signals the state of the control input and facilitates diagnostics during operation. The box terminals allow for secure and easy connection of wires. The device is delivered without a heatsink, making it suitable for applications with low thermal load.

Technology Explained Simply
Zero-voltage switching means the relay activates at the next zero crossing of the mains voltage as soon as the control voltage is applied. This avoids switching arcs and reduces electromagnetic interference. The high I2t value of up to 18000 A²s enables high surge current resistance, which is important during sudden load peaks or short-circuit conditions. The peak blocking voltage is 1200 V or 1600 V, depending on the variant, and the insulation voltage is 4000 V, ensuring high electrical safety. The operating temperature range is from -20 °C to 40 °C, making the device suitable for use in demanding climatic environments.

Compatibility and Accessories
The semiconductor relay is designed for load voltages of AC 48–480 V, with a maximum load voltage up to AC 600 V. The load current is AC 50 A, with a maximum load current capacity up to 125 A (AC-51). The width is 45 mm, enabling compact mounting on a DIN rail. Optionally, a heatsink is available, which can be snapped onto the DIN rail to improve heat dissipation. Additionally, an overtemperature protection can be integrated by inserting a temperature limit switch (normally open) into the designated pocket at the bottom. This switch disconnects when the heatsink temperature exceeds 100 °C, protecting the device from thermal overload.

Mounting and Installation
The device is mounted on a DIN rail, with box terminals provided for wire connections. The terminal markings are clearly indicated: A1(+)/A2 for the control input, L1 for the mains connection, and T1 for the load output. Mounting is tool-free, as the device is simply clipped onto the rail. The touch protection class IP20 ensures that the terminals are protected against accidental contact, while the housing has a protection rating of IP40.

Advantages in Operation
The semiconductor relay offers wear-free operation, as there are no mechanical contacts. This results in a long service life and reduced maintenance requirements. Zero-voltage switching minimizes network disturbances and protects sensitive loads. The LED indicator allows for quick status checks. The DCB technology ensures efficient heat dissipation, increasing operational safety. Compatibility with various control voltages (DC 4–32 V) and load voltages (AC 48–480 V) makes the device flexible for use in various industrial environments. Compliance with the standard IEC/EN 60947-4-3 ensures safe and reliable performance in industrial operation.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1001372
qrcode für Dold 0057700 PH9260.91/100 AC48-480V AC50A semiconductor relay UH=DC4-32V