| Technical data |
| Auxiliary voltage | AC, AC/DC |
| Classification | Thermistor-Motorschutz |
| Enclosure design | Switch cabinet |
| Measuring range max. | > 3.8 kΩ |
| Output contacts | 2 C/O contacts |
| Width | 22,5 mm |
| Type | MK 9163N |
| Variant |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | AC 110 V |
| Terminal type | fixed terminal blocks with screw terminals |
| Approvals and Markings | UL-rec. C/US, UKCA, CCC |
| Variant | With RESET and test function via built in button and X1/X2 |
The Thermistor motor protection relay MK 9163N from Dold is an enclosure device for monitoring the temperature of electric motors and other machine components such as bearings, gearboxes, oils or coolants. It serves to prevent thermal overloads that may arise due to high switching frequency, heavy start-up, single-phase operation, impaired cooling or high ambient temperature. The device monitors up to six thermistors via a common input and responds with a fault condition when the pickup temperature is reached or when faults occur in the sensor circuit, such as wire break or short circuit. The output contacts are configured as
2 changeover contacts, enabling flexible integration into existing circuits. The auxiliary voltage is
AC 110 V, although the device can also be operated with AC/DC voltages. The width of
22.5 mm makes it suitable for standard enclosures. The function is based on the
standby current principle, where the output relay is not activated in the event of a fault, ensuring a safe and reliable fault indication.
Applications
The relay is primarily intended for use in industrial plants where thermal monitoring of motors and mechanical components is necessary. It is particularly suitable for applications where high switching frequency or difficult operating conditions lead to increased heat generation. Temperature monitoring can also be extended to other components such as bearings or gearboxes to detect wear or overheating at an early stage. The ability to monitor up to six thermistors simultaneously enables comprehensive monitoring of complex systems.
Functions and equipment in detail
The device features an
LED indicator for auxiliary voltage and contact position, visually signaling the operating status. The
Test/Reset button allows both fault acknowledgment and test function in normal operation, where the device indicates faults as long as the button is pressed. Additionally, a
remote reset function via X1/X2 is integrated, which can be activated via a potential- and voltage-free switch. In devices with fault memory, the fault condition remains even after the normal operating temperature is restored, until acknowledged via the reset function.
Technology explained simply
The input circuit detects a fault when the resistance of a thermistor reaches the pickup value of 3.2 to 3.8 kΩ or when the sensor circuit is interrupted (resistance > 3.8 kΩ). The reset values lie between 1.5 and 1.8 kΩ. The measurement circuit load is < 5 mW (at 1.5 kΩ), which is very low and minimizes disturbance of the measured temperature. The measurement voltage is a maximum of 2 V at 1.5 kΩ. The auxiliary voltage can range from 0.8 to 1.1 times the nominal voltage for AC, from 0.9 to 1.25 times for DC with 10 % ripple, and from 0.8 to 1.1 times for DC with 48 % ripple. The turn-on delay is less than 40 ms, the turn-off delay less than 100 ms. The maximum bridging time during auxiliary voltage failure is 20 ms.
Compatibility and accessories
The device is specified according to
EN 60947-5-1 and
EN 60947-8 and complies with certifications
UL-rec. C/US,
UKCA and
CCC. The connection terminals are designed as
fixed screw terminal blocks, with an optional variant available featuring plug-in terminal blocks. The conductor connection options include 2 x 1.5 mm² stranded wire with ferrule and plastic sleeve or 2 x 2.5 mm² solid wire according to DIN 46 228-1/-2/-3/-4. The output contacts are designed for an electrical life of 1.5 million switching operations at 4 A, AC 230 V, cosϕ = 0.6. The mechanical life is at least 30 million switching operations. The short-circuit withstand capability is specified according to IEC/EN 60947-5-1, with a 6 A gG/gL fuse required for openers and 10 A gG/gL for closers.
Mounting and installation
The device is designed for installation in enclosures and is connected via the fixed screw terminals. Mounting is carried out in standard enclosure construction with a width of 22.5 mm. The connection terminals allow connection of stranded or solid conductors according to DIN 46 228. The auxiliary voltage is supplied via terminals A1/A2, the measurement circuits via P1/P2, and the remote reset function via X1/X2.
Advantages in operation
The
reliable temperature monitoring enables early detection of overheating and thus prevents damage to motors and other components. The
fast fault localization via LED indicator and test function reduces downtime. The
remote reset function allows centralized fault acknowledgment, which is particularly advantageous in large installations. The
galvanic non-isolation between input and measurement input must be considered during installation, as this does not ensure electrical isolation between circuits. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is also from -20 °C to +60 °C. The maximum operating altitude is 2000 m above sea level. The insulation class is designed for pollution degree 4, with a nominal impulse voltage value meeting the requirements of the standard.