Further information for Dold 0057072 voltage relay AC16 2/3HZ 25-250V
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Nominal voltage max.
AC 1000 V, DC 900 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9054
Operate delay
Variant
Auxiliary voltage
AC/DC 80 - 230 V
Contact equipping
2 changeover contacts
Measuring range
AC 16 2/3 Hz 25 - 250 V
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overvoltage relay. Energized on trip. Time delay at setting value
The Dold voltage relay BA9054/010 AC16 2/3HZ 25-250V 0-20S is an overvoltage relay of the VARIMETER series, designed for monitoring single-phase DC and AC power networks. It serves for early detection of voltage anomalies to prevent damage to electrical installations and enhance operational safety. The device operates on the operating current principle and is suitable for use in industrial and railway applications. Adjustment is performed via rotary switches on the front of the device, enabling user-friendly and precise configuration.
Applications
The relay is designed for monitoring voltages in the range AC 16 2/3 Hz from 25 to 250 V. It can be used both as an overvoltage relay and as an undervoltage relay, with the hysteresis depending on the set threshold value. The application is in industrial enclosures, where continuous monitoring of supply voltage is required to prevent failures due to voltage fluctuations. Galvanic isolation between auxiliary circuit and measurement circuit ensures safe and interference-free measurement.
Functions and Equipment in Detail
The device features 2 changeover contacts as output contacts, which can be used to control auxiliary circuits or alarm systems. The switching delay is 0 to 20 seconds and is activated once the set threshold is exceeded. This delay prevents false alarms caused by short-term voltage spikes. The response delay is also integrated to ensure stable reaction to voltage fluctuations. The auxiliary voltage can be supplied in AC or AC/DC operation at 80 to 230 V, enabling flexible integration into existing power supply systems.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measurement voltage. For AC voltages, the device is calibrated to the RMS value, ensuring accurate measurement even with sinusoidal voltages. Adjustment is performed via rotary switches, allowing both the response threshold and the hysteresis value to be manually set. The LED indicators signal the operating status: a green LED lights up when auxiliary voltage is applied, and a yellow LED indicates activation of the output relay. The width is 45 mm, enabling compact mounting in standard enclosures.
Compatibility and Accessories
The relay complies with standards IEC/EN 60255-1 and IEC/EN 60947-1. It holds UKCA and CCC certifications. The maximum rated voltage is AC 1000 V and DC 900 V, with measurement ranges varying depending on the version. The connection terminals are clearly labeled: A1/A2 for auxiliary voltage, e/f for measurement input, and contacts 11-14 and 21-24 for the two changeover contacts. Galvanic isolation between measurement and auxiliary circuit enhances safety and prevents interference.
Mounting and Installation
Mounting is performed in an enclosure, with the width of 45 mm allowing standard installation. The connection terminals are designed for secure connections. Adjustment of threshold values and hysteresis is done directly on the front of the device, requiring no additional tools or aids. Connection designations are detailed in the datasheet to ensure error-free installation.
Operational Advantages
Precise and reliable voltage monitoring increases operational safety. Early detection of voltage anomalies enables preventive maintenance and prevents costly failures. The integrated switching delay reduces false alarms, while the LED indicators provide a quick overview of the operating status. High overload capacity and measurement frequency up to 5 kHz make the relay suitable for demanding industrial applications.