| Technical data |
| Load current up to | 125 A |
| Load voltage up to | AC 600 V |
| Number of poles | 1-pole |
| On/Off Input Control | AC/DC, DC |
| Width | 45 mm |
| Type | PH 9260 |
| Variant |
| Control voltage | DC 4 - 32 V |
| Load current | AC 25 A |
| Load voltage | AC 48 - 480 V |
| Semiconductor output | 1-pole |
| Variant | Switching at zero crossing. With heat sink |
The Dold semiconductor contactor PH9260.91/000/01 is an
AC semiconductor relay with a load voltage of AC 48 to 480 V and a load current of AC 25 A. It is operated by a control voltage in the range of DC 4 to 32 V and is designed as a
zero-voltage switching device. The width is 45 mm, making it suitable for mounting on a standard DIN rail. The device is compliant with
IEC/EN 60947-4-3 and is used for wear-free and noiseless switching of loads in industrial applications.
Applications
This semiconductor relay is suitable for use in machines and plants in the plastics and rubber industry, packaging industry, soldering systems, and food industry. It is frequently used to control heating systems, electric motors, valves, and lighting systems. The zero-voltage switching function ensures that the load circuit is activated at the next zero crossing of the sinusoidal mains voltage, which increases the lifespan of the load and the relay and minimizes disturbances in the network.
Functions and Equipment in Detail
The device features two antiparallel-connected thyristors responsible for the switching function. The
DCB technology (Direct-Copper-Bonding process) ensures excellent heat transfer, reducing thermal stress on the component. An integrated
heat sink enables mounting on a DIN rail and provides optimal cooling. The status indication is provided by an
LED, which visually signals the state of the control input. The terminals are designed as
box terminals, enabling a secure and easy connection.
Technology Explained Simply
The zero-voltage switching function means that the relay does not switch the load circuit arbitrarily, but precisely at the voltage zero crossing. This avoids sparking and current surges, which is particularly beneficial for inductive loads such as motors or transformers. The peak blocking voltage is 1200 V or 1600 V, and the insulation voltage is 4000 V, enhancing electrical safety. The maximum load voltage is AC 600 V, and the maximum load current is 125 A, with the rated value for this item being 25 A. The limiting load integral (I²t) is up to 18000 A²s, describing the relay’s ability to withstand overload.
Compatibility and Accessories
The device is designed for mounting on a DIN rail and can optionally be equipped with an overtemperature protection. For this, a temperature limit switch (normally open) can be inserted into a designated pocket on the underside. An example is the temperature limit switch UCHIYA type UP62 – 100. The touch protection class is
IP20 at the terminals, and the enclosure protection rating is
IP40. The operating temperature range is between -20 °C and 40 °C, and the storage temperature range is between -20 °C and 80 °C.
Mounting and Installation
Mounting is done on a standard DIN rail. The box terminals allow for easy and secure connection of the wires. The LED indicator provides visual feedback on the operating status. Heat dissipation is supported by the integrated heat sink, ensuring efficient thermal management. Adhering to the specified temperature limits is important to ensure proper function.
Operational Advantages
The semiconductor relay offers wear-free operation, as there are no mechanical contacts. Switching operations are noiseless and allow for high switching frequencies. The DCB technology and heat sink ensure long service life and high reliability. Zero-voltage switching reduces electrical interference and protects the load from unwanted current surges. Compliance with the standard IEC/EN 60947-4-3 ensures safety and reliability in industrial use.