| Technical data |
| Approvals | UL |
| Load current up to | 50 A |
| Load voltage up to | AC 480 V |
| Number of poles | 1-pole, 2-pole, 3-pole |
| On/Off Input Control | DC |
| Width | 22,5 mm, 45 mm, 90 mm |
| Type | BF 9250/_ _8 |
| Variant |
| Auxiliary voltage | DC 4 - 32 V |
| Contact equipping | without signal contact |
| Load current | AC 25 A |
| Load voltage | AC 24 - 480 V |
| Semiconductor output | 1-pole |
| Approvals and Markings | UL-listed C/US |
| Variant | Switching at zero crossing. |
The Dold semiconductor contactor BF9250.91/008 UH=DC4-32V AC25A is a 1-pole, zero-voltage switching device for frequent and noiseless control of AC loads. It is used in industrial installations where reliable and maintenance-free switching functions for heaters, motors, valves or lighting are required. The device operates with a control voltage in the range of DC 4 to 32 V and switches load voltages of AC 24 to 480 V at a load current of up to 25 A. Switching occurs at the zero-voltage point of the alternating voltage, ensuring minimal network interference and a long service life of the load components. The design is compliant with IEC/EN 60947-4-2 and IEC/EN 60947-4-3 standards and carries the UL approval C/US, enabling use in certain markets.
Applications
This semiconductor contactor is designed for use in industrial and technical installations where high switching frequency and disturbance-free operation are required. Typical applications include control of heaters, electric motors, pneumatic or hydraulic valves, and lighting systems. Zero-voltage switching reduces electromagnetic interference and extends the service life of connected devices. The width of 22.5 mm allows for compact mounting on DIN rail, enabling efficient integration into enclosures and control systems.
Functions and Equipment in Detail
The device features a semiconductor output designed for operation with AC loads. Control is performed via digital actuation with DC voltage. The turn-on and turn-off delay is maximum 1 ms plus half a cycle of the supply voltage, which corresponds to approximately 10 ms at a frequency of 50 Hz. Switching occurs at the zero-voltage point, minimizing switching disturbances. The connection terminals are clearly labeled: A1/A2 for control voltage, L1/L2/L3 for supply connections, and T1/T2/T3 for load outputs. A green LED indicates that voltage is present at A1/A2.
Technology Explained Simply
The semiconductor contactor operates with an electronic circuit that switches the load at the zero-voltage point of the alternating voltage. This avoids spark formation and reduces electromagnetic interference. The switching is controlled by a zero-crossing detection circuit that determines the optimal switching time. Power loss is calculated using the formula P = 1.2 [V] x Ieff. [A] / k [W], where k is the form factor and equals 1.11 for sinusoidal current. The peak blocking voltage is ±1200 Vp, ensuring high insulation strength. Protection is provided by varistors with a varistor voltage of AC 510 V, which suppress overvoltages in the network.
Compatibility and Accessories
The device is available in various widths (22.5 mm, 45 mm, 90 mm) and pole configurations (1-, 2-, 3-pole). The 1-pole version is specified here. It is optionally available with a high I²t characteristic of the semiconductor to handle high switching currents (variant /1_8). The load voltage can reach up to AC 480 V, with the load current reaching up to 25 A at an ambient temperature of 40 °C. The operating temperature range is 0 to 40 °C, with a maximum temperature of 60 °C when considering the current derating factor. Storage is possible in the range of -20 to +80 °C.
Mounting and Installation
The device is mounted on DIN rail, with terminals for supply and load connections clearly labeled. The installation position is horizontal, with cooling fins oriented vertically. Mounting is done by clipping onto the rail, enabling quick and secure installation. The connection terminals are designed for cable connections, with a minimum load current of AC 40 mA. Creepage and clearance distances correspond to pollution degree 3 with a rated impulse withstand voltage of 4 kV according to IEC 60664-1.
Advantages in Operation
The semiconductor contactor provides a noiseless and wear-free switching function, which is particularly advantageous for frequent use. Zero-voltage switching minimizes electromagnetic interference and extends the service life of connected loads. The UL approval C/US enables use in certain markets. The integrated protection circuit with varistors protects the device against overvoltages. The compact design with a width of 22.5 mm allows for efficient space utilization in enclosures. Operational safety is ensured by compliance with IEC/EN 60947-4-2 and -4-3 standards.