Dold 0056453, EAN: 4030641564537

Dold 0056453 thermistor motor protection relay MK9163N.12/110 ATEX 230V

Dold 0056453 thermistor motor protection relay MK9163N.12/110 ATEX 230V

Lieske Part No. 1002257
Mfg Part No 0056453
EAN-Code 4030641564537
Manufacturer Dold
Here only 101,02 EUR
120,21 EUR incl. VAT

Further information for Dold 0056453 thermistor motor protection relay MK9163N.12/110 ATEX 230V

Technical data
Auxiliary voltageAC, AC/DC
ClassificationThermistor-Motorschutz
Enclosure designSwitch cabinet
Measuring range max.> 3.8 kΩ
Output contacts2 C/O contacts
Width22,5 mm
TypeMK 9163N ATEX
Variant
Contact equipping2 changeover contacts
Nominal voltageAC 230 V
Terminal typefixed terminal blocks with screw terminals
Approvals and MarkingsATEX
VariantWith short circuit detection. With RESET and test function via built in button and X1/X2
The Dold thermistor motor protection relay MK9163N.12/110 ATEX AC50/60HZ 230V is an enclosure device for monitoring the temperature of electric motors and other critical components in industrial installations. It serves to prevent thermal overloads that may arise due to high switching frequency, heavy start-up, single-phase operation, impaired cooling, or high ambient temperature. The device also monitors the temperature of bearings, gearboxes, oils, and coolants to enable early response to critical conditions. Its classification as a thermistor motor protection relay and its ATEX certification make it suitable for use in explosive atmospheres.

Applications
This relay is designed for use in industrial installations, particularly in environments where high operational safety and protection against thermal damage are required. It is used to monitor the temperature of electric motors, bearings, gearboxes, and coolants. The application takes place in enclosures, where the device can be mounted in standard control panels due to its width of 22.5 mm. The ATEX certification allows use in areas where explosion hazards exist due to flammable gases, vapours, or dusts.

Functions and Equipment in Detail
The device detects temperature exceedances, wire breaks in the sensor circuit, and short circuits in the sensor circuit. It features an input designed for connecting three or six thermistors. The operation is based on the rest current principle, where the output relay is not activated under normal conditions but only in the event of a fault. The output contacts consist of two changeover contacts, which can be used to control auxiliary functions or alarms. The status is indicated via LEDs, showing the auxiliary voltage status and contact position.

Technology Explained Simply
Monitoring is performed via thermistors, which act as temperature sensors. These resistors change their resistance value depending on temperature. The relay measures this resistance and compares it to a predefined threshold. If the threshold is exceeded, or if the sensor circuit is open or shorted, a fault is detected. The maximum measurement range exceeds 3.8 kΩ. The auxiliary voltage can be used in both AC and AC/DC operation, with the nominal voltage being AC 230 V. The terminal type consists of fixed terminal blocks with screw terminals, designed for connecting stranded wires up to 2 x 1.5 mm² with ferrules and plastic collars, or solid conductors up to 2 x 2.5 mm², in accordance with DIN 46 228-1/-2/-3/-4.

Compatibility and Accessories
The device is designed for use with thermistors, typically integrated into motors or other machine components. The connection options are designed for use with three or six thermistors. Variants include short-circuit detection, as well as reset and test functions, which can be activated via a button on the device and via terminals X1/X2. Optional plug-in terminal blocks are available, enabling quick device replacement.

Mounting and Installation
The device is mounted in enclosures and is designed for installation in standard control panels with a width of 22.5 mm. Installation is carried out using the provided screw terminals, with wire connections made in accordance with DIN 46 228-1/-2/-3/-4 standards. The terminals are designed for connecting stranded and solid conductors. Mounting is typically performed by qualified electricians, who must follow connection diagrams and safety instructions.

Advantages in Operation
The reliability of temperature monitoring enables early fault detection, increasing plant availability and preventing damage to motors or other components. Quick fault localization via LED indication and the ability to clear faults using the reset button or via X1/X2 reduces downtime. The ATEX certification expands the application range to hazardous areas, making the device suitable for a wide range of industrial applications. Compliance with standards such as EN 60947-5-1, EN 60947-8, EN 60079-14, EN 61508, EN 50495, and EN 13849 ensures the safety and reliability of the device.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1002257
qrcode für Dold 0056453 thermistor motor protection relay MK9163N.12/110 ATEX 230V