| Technical data |
| For single-phase motors, 230 V up to | 3 kW |
| For three-phase motors, 400 V up to | 5,5 kW |
| Load voltage up to | 3AC 230 / 400 V |
| Width | 45 mm |
| Type | BA 9010 |
| Variant |
| Mains / motor voltage | 3AC 110 V |
| Nominal motor power | 1,5 kW |
| Approvals and Markings | UKCA |
The Dold BA9010 3AC110V 1,5KW is an electronic soft starter for three-phase asynchronous motors, specifically developed for use in industrial drive systems. It enables a jerk-free and damage-free motor start by controlling the power supply to one of the three motor phases. The phase-cut control ensures that the current in this phase increases gradually, thereby building up the motor torque continuously. This avoids the sudden starting torque that occurs with direct switching. This protects mechanical drive components such as gearboxes, belts or chains from stress and increases the service life of drive parts. At the same time, the starting noise level is reduced, which is particularly beneficial for conveyor systems to prevent slippage or tipping of the conveyed goods.
Applications
This device is suitable for a wide range of industrial drives, including machines with gearbox, belt or chain drives, conveyors, fans, pumps, compressors, packaging machines, and door drives. It can also be used for limiting inrush current in single-phase transformers. The application is in systems where a soft start is required to minimize mechanical stress and increase operational safety.
Functions and Equipment in Detail
The BA9010 features separate adjustment options for the acceleration time and initial torque, allowing the start-up process to be adapted to the specific requirements of the respective system. Adjustments are made via an integrated control system, ensuring easy operation. The devices are equipped with LED indicators that visually display the operating status. After the start-up process is completed, the power electronics are bypassed via an internal relay contact to minimize power loss in the device and reduce operating temperature.
Technology Explained Simply
The operation is based on a single-phase motor control, where one of the three phases is controlled via phase-cut control. This allows the current in this phase to increase continuously, resulting in a smooth rise in torque. The control complies with standards IEC/EN 60947-4-2, ensuring reliability and safety in industrial environments. The width is 45 mm, enabling compact mounting on a 35 mm standard DIN rail. The device is designed for supply and motor voltages of 3AC 110 V and can drive motors with a rated power of up to 1.5 kW at 110 V. For three-phase motors at 400 V, a maximum power of 5.5 kW is possible; at 230 V, the maximum power is 3 kW.
Compatibility and Accessories
The BA9010 can be combined with motor brake devices, making it suitable for applications requiring high demands on braking and control functions. The devices are designed for use in systems with an overvoltage category III and pollution degree 2. The protection rating IP 20 protects against contact with moving parts and against solid foreign objects, but not against water or dust. The operating temperature range is from 0 °C to +45 °C, and the storage temperature range is from -25 °C to +75 °C. Above 40 °C, power derating occurs at a rate of 2 % per degree Celsius up to a maximum of 60 °C.
Mounting and Installation
Mounting is done by clipping onto a 35 mm standard DIN rail, enabling easy and quick integration into existing enclosures. No neutral conductor is required, simplifying installation. The terminal connections are rated for max. 2 x 2.5 mm² fine-stranded wire. The devices are intended for use in installation class 3, ensuring high safety during mounting and maintenance.
Operational Advantages
The soft start reduces mechanical stress on drive components, increasing the service life of motors and mechanical parts. Easy mounting allows for retrofitted integration into existing systems without requiring extensive modifications. In simple applications, a frequency converter can often be omitted, reducing system costs. The bypassing of the power electronics after start-up minimizes power loss and contributes to energy efficiency. The devices are designed for a maximum switching frequency of 100/h at 5 x Ie and 5 s t_on, ensuring high operational reliability in demanding environments.
Approvals and Markings
The device carries the UKCA marking, confirming compliance with applicable European safety and quality requirements. Compliance with the standard IEC/EN 60947-4-2 ensures reliability and safety in industrial use.