Further information for Dold 0056204 BA9054/331 DC0,12-1,2V UHDC110-220V battery symmetry monitor
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
DC 220 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9054/331
Operate delay
Variant
Contact equipping
2 changeover contacts
Measuring range
DC 0,12 - 1,2 V
Nominal voltage
DC 110 - 220 V
Start up delay
Without
Switching delay
10 s
Approvals and Markings
UKCA, CCC
Variant
Without separately auxiliary voltage
The battery symmetry monitor BA9054/331 from Dold is a specialised monitoring device for battery systems with central tapping, particularly in emergency power supplies. The device monitors the voltage symmetry of the two half-voltages of a battery and detects faults early, such as voltage inversion of individual cells, internal short circuits or sulfation. By providing early warning of deviations, it enables preventive maintenance measures to avoid costly failures. It is designed in enclosure format and has a width of 45 mm, making it suitable for standard control panels.
Applications
The BA9054/331 is used in industrial and technical installations where high operational reliability and availability of the emergency power supply are required. Typical applications include power plants, telecommunications centres, hospitals or industrial production facilities, where a sudden power failure can lead to serious consequences. The device is specifically designed for battery systems with central tapping to monitor voltage symmetry between the two halves of the battery.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which switch when a symmetry deviation is detected for more than 10 seconds. The response delay is 10 seconds to filter out short-term voltage fluctuations and avoid false alarms. The measurement ranges are adjustable to DC 0.12 to 1.2 V, DC 0.2 to 2 V or DC 1 to 10 V, with the specified type using the range DC 0.12 to 1.2 V. The reset values are fixed at 98 % of the response value, ensuring a high repeatability accuracy of ≤ ±0.5 %. The contacts are gold-plated, making them suitable for switching small loads, for example in the range of 1 mVA to 7 VA or 1 mW to 7 W at voltages of 0.1 to 60 V and currents of 1 to 300 mA.
Technology Explained Simply
The BA9054/331 measures the arithmetic mean of the voltage at the central tapping of the battery. If the difference between the two half-voltages exceeds the set response value for more than 10 seconds, the output relay switches. This can also occur in the event of a wire break at terminal M. The temperature dependence is < 0.05 % per Kelvin, ensuring stable operation over a wide temperature range. The current consumption in the central line is maximum 12 μA, keeping the battery load minimal. The operating voltage is drawn directly from the battery, with the nominal voltage ranging from DC 110 V to DC 220 V.
Compatibility and Accessories
It is therefore independent of additional power supplies and can be connected directly to the battery. The terminal designations are clearly defined: A1/A2 for auxiliary voltage (here battery voltage), UB+ and UB- for battery connections, M for central tapping and e as reference point for adjustment. The output contacts are designed as two changeover contacts, with contacts 11-12-14 and 21-22-24 representing the two changeover contacts.
Mounting and Installation
The device is mounted in enclosures and requires a width of 45 mm. The connection terminals are designed for direct connection to the battery terminals and the central tapping. Adjustment is performed by measuring the battery half-voltages, with readjustment after operating time possibly required, as new batteries are initially asymmetrical. The test button on the device front allows functional testing, which must be pressed for at least 10 seconds.
Advantages in Operation
By enabling preventive maintenance, the device increases operational reliability and ensures the availability of the system. The LED indicators (upper green LED for operational readiness, lower green LED for activated output) provide visual feedback on the operating status. The high repeatability accuracy and low temperature dependence ensure reliable measurement results. The gold-plated contacts allow switching of small loads, although with higher switching currents the gold plating may burn off, rendering the device unsuitable for small loads afterwards.
Approvals and Markings
The device complies with the standard IEC/EN 60255-1 and carries the approvals UKCA and CCC. These approvals confirm compliance with the applicable safety and functional requirements for electrical measuring instruments in industry.
Battery symmetry monitor is the product type, monitoring of battery systems the core function, central tapping the technology, IEC/EN 60255-1 the standard, 2 changeover contacts the contact configuration and DC 0.12–1.2 V the measurement range.