Further information for Dold 0056196 soft start brake 15 kW DC24V
Technical data
Extra functions
Mains monitoring, Temperature monitoring
For three-phase motors, 400 V up to
15 kW
Load voltage up to
3AC 480 V
Width
90 mm
Type
BI 9028
Auxiliary voltage required
Signalling output
Variant
Auxiliary voltage
AC 230 V
Contact equipping
2 x 1 changeover contact
Mains / motor voltage
3AC 200 - 480 V
Nominal motor power
15 kW
Approvals and Markings
UKCA
Variant
Volt free contacts for Start (X1/X4) and Stop (X3/X4) or motor on (x1/x4) and brake on (X3/X4)
The Dold soft starter with braking function BI9028.38/001 is an electronic control device for gentle starting and braking of three-phase and asynchronous motors. It is designed for motors with a rated power up to 15 kW at a supply voltage of 3AC 400 V and supports a load voltage up to 3AC 480 V. The auxiliary voltage is AC 230 V, although the device can also be operated with a DC 24 V auxiliary voltage. The width is 90 mm, enabling space-saving installation in enclosures. The device complies with the standard IEC/EN 60947-4-2 and is equipped with UKCA approval.
Applications
This device is used in systems requiring gentle motor starting and braking to minimize mechanical stress. These include machines with gear, belt, or chain drives, conveyor belts, fans, pumps, compressors, woodworking machines, centrifuges, packaging machines, and door drives. The application is particularly beneficial where direct starting or sudden braking could cause mechanical stress or damage.
Functions and equipment in detail
The BI9028.38/001 enables gentle starting and controlled braking in a single device. Control is achieved via two motor phases, regulated by thyristors using phase-cut control. This allows currents and motor torque to increase gradually, ensuring a smooth start-up. The start-up and braking time, as well as the start-up and braking torque, can be adjusted independently. The control contacts are potential-free and serve to signal start (X1/X4) and stop (X3/X4) or motor on (X1/X4) and brake on (X3/X4). The contact configuration includes 2 x 1 changeover contact.
Technology explained simply
The power electronics of the device operate with a 2-phase motor control, where two of the three motor phases are controlled via thyristors. The third phase is connected directly. This enables controlled current supply, reducing starting torque and thus minimizing mechanical stress in the drive. The mains monitoring detects phase failure and incorrect phase sequence, preventing damage to the motor or drive. Temperature monitoring is performed via a thermistor input (P1, P2, P3), which can be optionally used. The LED indicators signal the operating status: a green LED remains lit when the auxiliary voltage is present and blinks during start-up and braking. A yellow LED indicates the status of the alarm relays.
Compatibility and accessories
The device is designed for 3-phase motors operating in the voltage range of 3AC 200 to 480 V. It requires an auxiliary voltage of AC 230 V but can also be operated with DC 24 V. Mains monitoring and temperature monitoring are integrated functions. The alarm relays (2 x 1 changeover contact) are used for status and fault indication. No external motor or brake contactor is required, as the functions are integrated into the device.
Mounting and installation
The device is mounted in enclosures and is designed for installation in standard control panels. The width of 90 mm allows for compact placement. The terminal connections are clearly labeled: A1/A2 for auxiliary voltage, A3(+)/A4 for DC 24 V, X1/X2/X3/X4 for control, P1/P2/P3 for thermistor, 11/12/14 and 21/22/24 for alarm relays, and T1/T2/T3 for motor connections. Wiring is carried out according to the circuit diagrams included in the data sheet.
Advantages in operation
Due to the integrated soft start and braking function, the service life of drive components is extended, as mechanical stress during start-up and braking is reduced. Simple wiring and galvanically isolated control with a voltage range up to AC/DC 230 V simplify installation. Mains and temperature monitoring increase operational safety. The LED indicators allow quick status monitoring without additional measuring instruments. The device is designed for use in industrial systems, where reliability and ease of maintenance are important.