Further information for Dold 0055712 MK9040N.12/001 asymmetrical relay 3AC400V 50/60Hz
Technical data
1- / 3-phase
3
Enclosure design
Switch cabinet
Measuring range max.
3 AC 400 V
Output contacts
2 C/O contacts
Standard measuring range
3 AC 400 V
Width
22,5 mm
Type
MK 9040N
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3AC 400 V 50/60 Hz
Terminal type
screw terminals fixed
Time delay
without
Approvals and Markings
UKCA
Variant
With phase sequence detection. Without time delay
The Dold asymmetry relay MK9040N.12/001 3AC400V 50/60HZ is a monitoring device of the VARIMETER series, specifically developed for the control of three-phase networks. It is designed to detect voltage asymmetry, phase failure, reverse voltage, and incorrect phase sequence, ensuring the operational safety and availability of installations such as elevators, escalators, or crane systems. The device is designed for use in enclosures and features a width of 22.5 mm, enabling compact mounting on a DIN rail in accordance with IEC/EN 60715.
Applications
This relay is used in industrial and technical installations where the reliability of three-phase power supply is critical. It is particularly suitable for drives where incorrect rotation direction due to reversed phase sequence can cause damage. Early detection of disturbances such as asymmetry or phase failure enables preventive maintenance and prevents costly downtimes.
Functions and equipment in detail
The device monitors a three-phase network with a rated voltage of 3 AC 400 V at a frequency of 50/60 Hz. It detects voltage asymmetries in the range of 5 to 15 %, with a repeat accuracy of ≤ 0.5 %. The dropout ratio is below 4 % of the rated voltage. Reverse voltage detection occurs up to 100 % minus the set value, for example, up to 95 % when the set value is 5 %. The MK9040N.12/001 variant includes phase sequence detection, but without response delay. The output contacts consist of two changeover contacts, which can be used for controlling auxiliary contacts or warning signals.
Technology explained simply
The input side of the relay receives voltage from the three-phase network and analyzes the voltage relationships between phases L1, L2, and L3. Upon detection of a disturbance, such as asymmetry exceeding the set threshold, the relay switches the output contacts. The response delay is not activated in this variant, meaning the reaction occurs immediately. The device indicators consist of two LEDs: the upper LED indicates that the operating voltage is present, while the lower LED signals the state of the output relay.
Compatibility and accessories
The relay is designed for use with conductors of 2 x 2.5 mm² solid or 2 x 1.5 mm² stranded wire with ferrules in accordance with DIN 46228-1/-2/-3/-4. The terminal type is fixed with screw terminals, requiring a stripping length of 10 mm and a tightening torque of 0.8 Nm. Optional plug-in connection blocks are available, enabling quick replacement of the device. The devices are specified in accordance with IEC/EN 60255-1 and carry the UKCA mark.
Mounting and installation
Mounting is performed on a DIN rail within the enclosure. The terminals are designed for securing solid or stranded conductors. The connection terminals are clearly labeled (L1, L2, L3 as well as contact designations 11, 12, 14, 21, 22, 24), enabling simple and error-free wiring. The device dimensions are 22.5 mm (width) × 90 mm (height) × 100 mm (depth).
Advantages in operation
Through continuous monitoring of the three-phase network, the relay ensures high operational safety. Correct rotation direction of drives is guaranteed by phase sequence detection. Simple wiring and clear indication via LEDs facilitate commissioning and maintenance. Compliance with the standard IEC/EN 60255-1 and UKCA approval ensure conformity with European requirements.