Dold 0055532, EAN: 4030641555320

Dold 0055532 BH5911.22/00MF0 DC24V base module

Industrial Material > Industrial relays and contactors > Electronic modules

Dold 0055532 BH5911.22/00MF0 DC24V base module

Lieske Part No. 780385
Mfg Part No 0055532
EAN-Code 4030641555320
Manufacturer Dold
Here only 765,67 EUR
911,15 EUR incl. VAT

Further information for Dold 0055532 BH5911.22/00MF0 DC24V base module

Technical data
ApplicationEmergency stop, Light barrier
Cat. / PL acc. to EN ISO 13849-14/e
SIL CL acc. to IEC/EN 620613
SIL acc. to IEC/EN 620613
Safe output contacts, redundant NO contacts2, 3
Width45 mm
TypeBH 5911
Variant
Contact equipping2 NO contacts, 1 NC contact
Nominal voltageDC 24 V
Approvals and MarkingsCSA C/US, TÜV, CCC
The Dold BH5911.22/00MF0 DC24V is a base module of the SAFEMASTER M safety system, developed for implementing safety-related control circuits in machine and plant engineering. It serves the protective function for personnel and machines by monitoring and controlling safety functions such as emergency stop, light grids, or safety doors. The device is designed for use in industrial environments and meets the requirements for safety functions up to Category 4 and Performance Level e according to EN ISO 13849-1 as well as SIL 3 according to IEC/EN 62061. The nominal voltage is DC 24 V, and the width of 45 mm allows for compact mounting in standard control panels.

Applications
This module is used in various industries, including paper and printing industry, forming technology, beverage, food, and packaging industry. It is suitable for machining centers, robotic systems, machine tools, injection molding and packaging machines, as well as complete production lines. The functionality includes monitoring of emergency stop switches, light barriers, safety doors, and two-hand controls. It can be configured for immediate shutdown or controlled shutdown with time-delayed output contacts.

Functions and Equipment in Detail
The module features contact configuration with 2 NO contacts and 1 NC contact, where the output contacts are designed to be safe and redundant. The functions are switched via rotary switches, enabling simple configuration without a programming device. It supports various operating modes, including Auto-Start, Hand-Start, and parallel connection of multiple SAFEMASTER M systems. The inputs can be configured for 4 start buttons, 3 start and 1 stop button, or 2 emergency stop buttons. The outputs offer 3 NO contacts or 2 NO contacts with 1 NC contact as a signaling contact.

Technology Explained Simply
The device continuously monitors the status of connected safety functions. This includes over- and under-voltage monitoring, wire break and short-circuit monitoring, as well as a continuously monitored feedback circuit for connecting external contactors. Faults are indicated via LEDs and semiconductor outputs, enabling quick diagnosis. System messages can be forwarded to other bus participants via an optional fieldbus connection. Configuration is done through simple switch settings, eliminating the need for special software or programming devices.

Compatibility and Accessories
The module is part of the modular SAFEMASTER M system and can be combined with additional input and output modules. The assignment of input to output functions is freely configurable, with hierarchical group formation possible. System expansion is achieved via expansion modules, enabling up to 26 single-channel or 13 dual-channel input circuits. Output groups can operate separately, jointly, or hierarchically as desired.

Mounting and Installation
The module is mounted in standard control panels and requires no special tools for installation. The connection points are designed for wiring safety functions. Configuration is done via internal switches, which are adjusted using a screwdriver. Mounting typically occurs in enclosures that comply with relevant standards.

Advantages in Operation
The module offers a flexible and cost-efficient solution for implementing complex safety functions without high wiring effort. The simple configuration without programming reduces setup time and maintenance costs. The integrated diagnostic function via LEDs and semiconductor outputs enables quick fault detection. The modular expandability and compatibility with existing fieldbus systems increase flexibility when adapting the system. Certifications CSA C/US, TÜV, and CCC confirm compliance with international safety standards.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/780385
qrcode für Dold 0055532 BH5911.22/00MF0 DC24V base module