Dold 0055396, EAN: 4030641553968

Dold 0055396 insulation monitor 220-240V

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Dold 0055396 insulation monitor 220-240V

Lieske Part No. 371886
Mfg Part No 0055396
EAN-Code 4030641553968
Manufacturer Dold
Here only 251,89 EUR
299,75 EUR incl. VAT

Further information for Dold 0055396 insulation monitor 220-240V

Technical data
Enclosure designSwitch cabinet
IMD typeAC
Nominal voltage IT systemAC 0 - 500 V
Response value5 - 500 kΩ
Response value typeAdjustable
Width35 mm
TypeSL 5880
Earth fault indicatorYes
Variant
Alarm value5 - 100 kOhm
Auxiliary voltageAC 220 - 240 V 50 - 400 Hz
Contact equipping2 changeover contacts
Prewarning valueWithout
Approvals and MarkingsUKCA
VariantAdjustable alarm value. De-energized on trip
The insulation monitor SL5880.12 from Dold is a device for monitoring the insulation resistance in ungrounded AC and three-phase networks (IT systems) with a rated voltage of AC 0 to 500 V. The device operates on the principle of residual current, where the output relay remains inactive in the event of a fault and stays in the resting state. The auxiliary voltage is AC 220 to 240 V at a frequency of 50 to 400 Hz. The trigger values are adjustable via a potentiometer on the front of the device, with the alarm threshold ranging from 5 to 100 kΩ. Monitoring is carried out in accordance with the standard IEC/EN 61557-8, which applies to the measurement of insulation resistance in electrical installations.

Applications

The insulation monitor is designed for pure AC and three-phase networks operating in the frequency range of 10 to 10000 Hz. It is particularly suitable for industrial applications as well as railway installations. The separate supply voltage allows monitoring of de-energized systems, for example, when consumers such as motor windings must be switched on in an emergency. The device variant SL5880.12 is designed for enclosures, with connection terminals located at the top and a depth of 98 mm.

Functions and Equipment in Detail

The device features two changeover contacts as contact configuration, used for signal transmission in the event of earth faults. Indication is provided via LEDs: a green LED indicates operational readiness, while a red LED signals an insulation fault when the measured resistance falls below the set alarm threshold. The function of the output relays is programmable, allowing selection between memory behavior and hysteresis behavior. With memory behavior, the fault condition is stored until reset via the integrated reset and test button or external buttons. With hysteresis behavior, the fault condition is automatically reset as soon as the insulation resistance rises above the alarm threshold.

Technology Explained Simply

The insulation monitor measures the resistance between the electrical network and earth to detect earth faults early. An excessively low insulation resistance can lead to short circuits, fire hazards, or system failures. The galvanic isolation between the measurement circuit, auxiliary voltage, and output contacts ensures safe and interference-free measurement. The alarm threshold is adjusted via a potentiometer, allowing the operator to adapt the threshold according to specific requirements. The width is 35 mm, enabling mounting on a DIN rail or via screw mounting.

Compatibility and Accessories

The device is designed for enclosures and can be connected to external reset and test buttons to simplify operation in larger installations. It is part of the VARIMETER IMD series and is available in various variants (IL 5880, IP 5880, SL 5880, SP 5880), with SL5880.12 representing the variant for enclosures with top-mounted connection terminals. The UKCA certification is indicated, enabling use in the EU and the United Kingdom.

Mounting and Installation

Mounting is either on a DIN rail or via screw mounting. The depth of 98 mm and top-mounted connection terminals are designed for enclosures with mounting plate and cable duct. The connections are clearly labeled: L and N for the monitored IT network, PE for the protective conductor, PT for the external test button, and LT1/LT2 for external reset buttons or programming.

Advantages in Operation

The insulation monitor provides preventive protection against fires and system failures by early detection of insulation faults. The simple adjustment of the alarm threshold and clear LED indication simplify maintenance and monitoring. The ability to monitor de-energized systems expands the application range in emergency and backup systems. The programmability of the relay function allows adaptation to specific requirements of individual installations.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/371886
qrcode für Dold 0055396 insulation monitor 220-240V