Further information for Dold 0055288 IK9171.11/240 3/N AC415/240V 0,75UN undervoltage relay
Technical data
1- / 3-phase
1, 3
Auxiliary voltage
Without
Enclosure design
Distribution board
Nominal voltage max.
3/N AC 500 / 290 V
Output contacts
1 C/O contact
Width
17,5 mm
Type
IK 9171
Operate delay
Variant
Contact equipping
1 changeover contact
Nominal voltage
3/N AC 415 / 240 V
Response value
0,75 Un
Time delay
5 - 15 min
Approvals and Markings
UKCA
Variant
With N. NC circuit operation. Settable time delay t2. Fixed response value
The Dold undervoltage relay IK9171.11/240 is an electrical monitoring device for detecting undervoltage in three-phase AC networks. It is designed for use in installation distributor configurations and serves for network monitoring as well as automatic switching to safety power supply or safety lighting in accordance with DIN VDE 0100-710 and DIN VDE 0108. The device operates on the stand-by current principle, in which the output relay is not activated in the event of a fault, and requires no auxiliary voltage. It features an LED indicator that visually signals the status of the output relay.
Applications
This relay is primarily designed for monitoring three-phase AC networks, but can also be connected in single-phase operation. It is used in systems where a safe and controlled response is required in the event of voltage dips or phase failure, for example in lighting systems, emergency power supplies, or for controlling consumers that must not be switched on immediately after a short network interruption, such as compressors or certain processing machines. The variant with time delay t2 for returning to normal condition is particularly suitable for unstable power networks, for example in local power generation or in networks of the 2nd and 3rd world, where consumer groups are to be switched on in stages after a defined waiting period.
Functions and Equipment in Detail
The device features contact configuration with one changeover contact (1 C/O contact). The pickup value is fixed at 0.75 times nominal voltage (Un). The nominal voltage is 3/N AC 415/240 V, with a maximum nominal voltage up to 3/N AC 500/290 V. The time delay t2 for returning to normal condition is adjustable and ranges from 5 to 15 minutes. Phase sequence is irrelevant, as the device operates independently of phase order. When connected without a neutral conductor, the arithmetic mean of phases L1 and L3 is measured against L2 (IK/SK 9171). In single-phase operation, terminals L1, L2, and L3 must be bridged.
Technology Explained Simply
The relay monitors the voltage in the network and reacts when the voltage drops below the fixed pickup value of 0.75 Un. Upon detection of a fault, the output relay switches contact 11-14 (closed) and activates the LED indicator. The time delay t2 ensures that after voltage restoration, the load is not switched on immediately, but only after a defined waiting period (5–15 min). This prevents damage caused by uncontrolled restart of consumers. The hysteresis is approximately 4 %, meaning that return to normal condition only occurs when the voltage exceeds the pickup value, to avoid chattering.
Compatibility and Accessories
The device is designed for use in installation and industrial distributors according to DIN 43 880. It is available in I-type construction, featuring a mounting depth of 59 mm and terminals located at the bottom. The mounting width is 17.5 mm. It is compatible with three-phase networks with neutral conductor connection (3/N AC) and can also be used in single-phase installations. The device variant is specified according to IEC/EN 60255-1 and bears the UKCA mark.
Mounting and Installation
Mounting is performed in standard installation distributors with DIN rail. The terminals are located at the bottom, enabling easy integration into existing distributors. The mounting width of 17.5 mm allows for compact placement. The devices are designed for frequencies between 45 and 65 Hz and can be operated continuously with an overload of 1.15 times nominal voltage.
Advantages in Operation
The relay provides reliable network monitoring without auxiliary voltage and using the stand-by current principle, increasing safety. The adjustable time delay t2 enables controlled restart of consumers. The LED indicator allows for quick visual fault detection. Compatibility with single- and three-phase networks, as well as independence from phase sequence, increases operational flexibility. The mounting width of 17.5 mm and I-type construction facilitate integration into existing control systems.