Dold 0054759, EAN: 4030641547592

Dold 0054759 SL9079.12/002 voltage relay 0.2-2s

Dold 0054759 SL9079.12/002 voltage relay 0.2-2s

Lieske Part No. 1002212
Mfg Part No 0054759
EAN-Code 4030641547592
Manufacturer Dold
Here only 279,94 EUR
333,13 EUR incl. VAT

Further information for Dold 0054759 SL9079.12/002 voltage relay 0.2-2s

Technical data
1- / 3-phase1, 3
Auxiliary voltageWithout
Enclosure designSwitch cabinet
Nominal voltage max.3 AC 500 V
Output contacts2 C/O contacts
Width35 mm
TypeSL 9079
Operate delayYes
Variant
Contact equipping2 changeover contacts
Nominal voltage3AC 230 / 400 V
Response value0,55 - 1,05 Un
Time delay0,2 - 2 s
VariantFür Netze mit Neutralleiter. Einstellbarer Rückfallwert
The Dold voltage relay SL9079.12/002 is a monitoring device for three-phase power networks, specifically designed for detecting short-term voltage interruptions. It ensures a defined operating state in control systems, particularly in contactor and PLC systems, where short-term network disturbances can lead to uncontrolled states. The device monitors voltage in 3-phase networks with neutral conductor (3/N AC 230/400 V) and detects interruptions starting from a duration of 20 ms. Upon detection of a disturbance, an extended reset pulse is generated to return control units to a safe initial state and prevent unwanted restarts.

Applications
This relay is intended for use in industrial enclosures and is particularly suitable for systems that rely on stable network voltage. It is used in industrial automation technology to increase the reliability of controls and drives. The function is especially useful in systems that must not automatically restart during short-term voltage dips, such as production lines or systems with safety functions.

Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which drop out in the event of a fault. The pickup values are adjustable within a range of 0.55 to 1.05 times nominal voltage (Un), allowing flexible adaptation to different network conditions. The re-energizing delay is also adjustable and ranges from 0.2 to 2 seconds. This enables the generation of a defined reset pulse, ensuring that all control components are reset synchronously. The green LED indicator signals the good condition, meaning the output relay is activated and the voltage is within the specified range.

Technology Explained Simply
The relay operates on the principle of rest current, meaning that the output relay is not activated in the event of a fault, but drops out. Voltage measurement is performed against the neutral conductor (N), with phase sequence being arbitrary. For single-phase connection, terminals L1, L2, and L3 must be bridged. Voltage interruption detection starts at a duration of 20 ms with a drop value of 0.8 Un. The response time is approximately 40 ms at a drop value of 0.8 Un. The hysteresis is 4 % to avoid switching due to minor voltage fluctuations.

Compatibility and Accessories
The device is designed for networks with a neutral conductor and can also be connected in single-phase mode. It is compliant with IEC/EN 60255-1 and suitable for enclosures with mounting plate and cable duct. The SL 9079 housing type has a depth of 98 mm and top-mounted connection terminals. The width is 35 mm. It can also be configured for fault memory (re-energizing lockout), preventing automatic restarts.

Mounting and Installation
Mounting is carried out in enclosures with a mounting plate. The connection terminals are located at the top, facilitating wiring in cable ducts. The nominal frequency is 50/60 Hz, and the nominal consumption is approximately 8 VA. The input resistances are approximately 150 kΩ. The maximum overload capacity is 1.1 times nominal voltage continuously.

Operational Advantages
The adjustable re-energizing delay and fast detection of voltage interruptions increase operational safety. The device enables preventive maintenance, as it detects and documents disturbances early. Its use in combination with PLC systems or contactor controls ensures that the entire system returns to a defined state after a disturbance, increasing productivity and preventing damage from uncontrolled restarts. The green LED indicator provides a visual status overview, simplifying maintenance and diagnostics.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1002212
qrcode für Dold 0054759 SL9079.12/002 voltage relay 0.2-2s