Further information for Dold 0054747 SK9273.11 undercurrent relay AC220-240V
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Output contacts
1 C/O contact
Width
17,5 mm
Type
SK 9273
Operate delay
Variant
Auxiliary voltage
AC 220 - 240 V
Contact equipping
1 changeover contact
Measuring range
1 - 10 A
Switching delay
0,1 - 20 s
Variant
1-phasiges Stromrelais. Ruhestromprinzip. Nicht speichernd
The Dold undercurrent relay SK9273.11 is a single-phase measuring and monitoring device for alternating current networks, designed for use in enclosures. It monitors the load current in the range of 1 to 10 A and switches the output contact when a settable threshold value (0.1 to 1 times the nominal measurement range) is undershot. The device operates according to the zero-current principle, whereby the output relay is not activated in the event of a fault, enabling safe reset without external reset measures. The switching delay is continuously adjustable between 0.1 and 20 seconds to avoid unwanted switching operations during brief current drops. The hysteresis is fixed at approximately 4 %, ensuring stable switching behavior without oscillations. The LED indicators signal the presence of auxiliary voltage (green) and the position of the output contact (yellow), allowing the operating status to be visually checked.
Applications include monitoring motors, pumps, heaters, or other consumers where a sudden current drop may indicate a fault or interruption. The device is suitable for use in industrial and commercial installations where reliable current monitoring is required. The housing design is intended for enclosures, with a depth of 98 mm and top-mounted connection terminals, enabling installation on a mounting plate with cable duct. The width is 17.5 mm, allowing compact placement in standard switchboards.
Functions and equipment in detail include continuous adjustment of the threshold value within the measurement range, high accuracy of ≤ ±1 % for repeatability, and temperature influence of ≤ 0.2 % per Kelvin. The auxiliary voltage is AC 220 to 240 V, with a nominal consumption of 5.5 VA at 230 V. The output contacts consist of a 1 changeover contact, rated for switching operations up to 3 A (make) and 1 A (break) at AC 230 V. The electrical life is at least 300,000 switching cycles at 1 A and AC 230 V, while the mechanical life exceeds 100 million switching cycles. Short-circuit resistance is ensured by a maximum fuse rating of 4 A gG/gL.
Technology explained simply shows that the device continuously measures the current flow in a conductor. When the current falls below the set threshold, the output contact is opened after an adjustable delay time. The hysteresis ensures that the contact is only closed again when the current rises above a value 4 % lower. This prevents rapid, unwanted switching on and off with slightly fluctuating loads. The LED indicators provide visual feedback on whether auxiliary voltage is present and whether the contact is closed or open.
Compatibility and accessories refers to the various variants of the series. The device is available in two housing forms: IK 9273 (for installation and industrial distributors) and SK 9273 (for enclosures). The SK 9273 variant, as described here, is designed for enclosures with mounting plate and cable duct. Measurement ranges extend from 0.05 to 10 A, with higher currents measurable via an external current transformer (2.5 VA). Compliance with standards is according to IEC/EN 60255, ensuring adherence to international standards for measuring and monitoring devices. The protection rating of the housing is IP 40, and the terminals are IP 20, providing protection against touch and dust, but not against water.
Mounting and installation is carried out in enclosures with a mounting plate. The top-mounted connection terminals allow easy wiring via a cable duct. The depth of 98 mm requires sufficient space in the enclosure. The devices are designed for continuous operation and can be operated in a temperature range of -20 to +60 °C. EMC compatibility is tested according to IEC/EN 61000-4-2 to -4-6, ensuring resistance to electromagnetic interference.
Operational advantages include high reliability, simple adjustability, and clear visual indication. The non-memory function with zero-current principle enables automatic reset as soon as the current exceeds the threshold again. The long service life and high switching durability reduce maintenance and replacement requirements. Compliance with the IEC/EN 60255 standard ensures suitability for professional applications.