| Technical data |
| Enclosure design | Front panel mounting |
| Output contacts | 1 C/O contact |
| Time function(s) | Off-delay, with control signal |
| Width | 72 mm |
| Type | EF 7666 |
| Variant |
| Contact equipping | 1 NO contact undelayed, 1 NO contact delayed, 1 NC contact undelayed, 1 NC contact delayed |
| Nominal voltage | AC 127 V |
| Time range | 0,15 s - 30 h |
The Dold time relay EF7666.24 is a delayed-release industrial time relay for front panel mounting, designed for a rated voltage of AC 127 V at a frequency of 50/60 Hz. It is used for time-delayed control of electrical devices and systems, particularly to account for the coast-down behavior of motors or other system components. The delay time can be continuously adjusted within a range of 0.15 seconds to 30 hours, with six switchable time ranges accessible from the front via a rotary switch. The time function operates on the principle of delayed release with control signal, in accordance with standard EN 61812-1. The time progress indicator allows visual monitoring of the timing process, and the contact position indicator shows the current state of the contacts.
Applications
This device is designed for industrial control tasks where time-delayed deactivation is required. Typical applications include the control of fans, pumps, lighting systems, or other drives, where immediate deactivation after the control signal is not desired. The voltage failure safety ensures that the relay remains in the de-energized position in case of power failure, which is important for safety in industrial installations.
Functions and Equipment in Detail
The time relay features a contact configuration with one instantaneous closer, one delayed closer, one instantaneous opener, and one delayed opener, which together form a changeover contact. The contacts are made of AgNi with a gold plating layer of 0.2 μm, ensuring high switching capacity and long service life. The operating time of the contacts is less than 35 ms, and the release time is less than 60 ms. The repeatability accuracy is ≤ ± 0.5 % of the scale end value, with a permissible deviation of ≤ ± 1 % in the range of 3 and 6 seconds. The reset time is less than 150 ms.
Technology Explained Simply
The time delay is implemented mechanically via a rotary switch and a mechanical timing mechanism. Adjustment is made using a continuously adjustable pointer on an absolute scale, allowing precise setting of the delay time. The front of the device is splash-proof and meets protection class IP 65, enabling use in outdoor or humid environments. The width is 72 mm, and the front face measures 72 x 72 mm, allowing compact installation in standard control panels.
Compatibility and Accessories
The relay is designed for use in industrial control systems and can be combined with other devices from the MINITIMER series such as AA 7666, EC 7666, or EH 7666, depending on requirements for width and timing function. The input voltage is AC 127 V, with a voltage range between 0.8 and 1.1 times the rated voltage. The rated frequency is switchable between 50 and 60 Hz. The maximum switching capacity is 3 A at AC 230 V (AC 15), and the electrical service life is 1 x 10⁵ switching operations at 3 A and 5 x 10⁵ at 1 A. The mechanical service life exceeds 30 x 10⁶ switching operations or 15,000 operating hours.
Mounting and Installation
The device is mounted for front panel installation, with connection terminals provided for supply voltage (A1-A2) and control signal (B1-B2), as well as output contacts (15-16, 27-28, 31-32, 43-44). Mounting is done in standard control panels with a width of 72 mm. The connection terminals are designed for secure connections, and the front is suitable for use in humid or dusty environments.
Operational Advantages
The continuous adjustment of the delay time over a wide range from 0.15 s to 30 h allows flexible adaptation to different applications. The mechanical timing mechanism is robust and maintenance-free. The IP 65 protection class ensures high reliability in demanding environments. Voltage failure safety and clear contact position indication enhance system safety and operational reliability. The contact configuration with a changeover contact enables flexible integration into existing circuits.