Dold 0054179, EAN: 4030641541798

Dold 0054179 semiconductor contactor 3xAC 10A

Dold 0054179 semiconductor contactor 3xAC 10A

Lieske Part No. 1001457
Mfg Part No 0054179
EAN-Code 4030641541798
Manufacturer Dold
Here only 323,16 EUR
384,56 EUR incl. VAT

Further information for Dold 0054179 semiconductor contactor 3xAC 10A

Technical data
ApprovalsUL
Load current up to50 A
Load voltage up toAC 480 V
Number of poles1-pole, 2-pole, 3-pole
On/Off Input ControlAC/DC, DC
Width22,5 mm, 45 mm, 90 mm
TypeBF 9250
Signalling outputYes
Temperature monitoringYes
Variant
Auxiliary voltageDC 24 V
Contact equippingwith signal contact
Load current3 x AC 10 A
Load voltageAC 24 - 480 V
Semiconductor output3-pole
Approvals and MarkingsUL-listed C/US
VariantSwitching at zero crossing. 3 semiconductor contactors with common ground for control inputs in one housing
The Dold semiconductor contactor BF9250.03/004 UH=DC24V 3xAC 10A is an electronic switching device for use in industrial applications, designed for noiseless and frequent switching of loads such as heaters, motors, valves, and lighting. It is a 3-pole variant with a control voltage of DC 24 V and a load voltage of AC 24 to 480 V. The load current is 3 x AC 10 A, while the BF 9250 series supports load currents up to 50 A. The device is zero-voltage switching, meaning the switching operation occurs at the zero crossing of the alternating voltage to minimize voltage spikes and electrical interference. Switching is performed via semiconductors, replacing a mechanical relay and thus ensuring a long service life and noiseless operation.

Applications
This semiconductor contactor is intended for use in industrial control and automation systems, particularly where high switching frequency and disturbance-free switching are required. It is suitable for applications in manufacturing industry, building automation, power supply, and machine control. The devices are designed for operation with AC loads and can switch loads up to 480 V. Zero-voltage switching reduces electromagnetic interference and extends the service life of connected devices.

Functions and Equipment in Detail
The device features an alarm output that signals during operation or malfunction. Integrated temperature monitoring of the power semiconductors protects the device from overheating. When a critical temperature is reached, the alarm output is activated, enabling early response to malfunctions. Control is performed via control input X1, which has low current consumption and is therefore suitable for control by PLC systems. Control can be performed via AC/DC or DC. Terminal markings include A1, A2, A3, A4, A5, A6, COM, X1, 18, 11, 12, L1, L2, L3, T1, T2, T3, with clear definitions for control and load connections.

Technology Explained Simply
The semiconductor contactor operates using an electronic circuit that switches the load via semiconductors (e.g. thyristors or triacs). Switching occurs at the zero crossing of the alternating voltage, minimizing spark generation and interference. Integrated temperature monitoring monitors the heat development of the semiconductors and activates the alarm output when a predefined threshold is exceeded. Protection circuitry using varistors protects the device against overvoltage. The width is 90 mm, enabling mounting on DIN rail. LED indicators (green, yellow, red) signal the operating status, with the green LED lighting when controlled via A1, the yellow LED when controlled via X1, and the red LED when temperature monitoring is triggered.

Compatibility and Accessories
The device is designed for use in systems with DIN rail mounting and can be combined with other devices from the BF 9250 series. Control is performed via standard control systems such as PLCs, with control input X1 having low current consumption. Approvals include UL-listed C/US, enabling use in the USA and Canada. Conformity with standards IEC/EN 60947-4-2 and IEC/EN 60947-4-3 ensures the safety and reliability of the device.

Mounting and Installation
Mounting is performed on a DIN rail, with the width of 90 mm to be considered. Connections are clearly labeled, with load connections (L1, L2, L3) and load outputs (T1, T2, T3) as well as control connections (A1, A2, X1) distinctly marked. Power supply is via the control voltage DC 24 V. LED indicators provide visual feedback on the operating status. Installation is carried out according to technical data and standard requirements.

Advantages in Operation
The semiconductor contactor offers noiseless switching, high switching frequency, and long service life. Zero-voltage switching reduces interference and extends the service life of connected loads. Integrated temperature monitoring and alarm output increase safety and enable early fault detection. Control via PLC systems and DIN rail mounting facilitate integration into existing control systems. Approvals according to UL and IEC standards guarantee the reliability and safety of the device.