Further information for Dold 0054077 current relay AC1,5-15A AC/DC24-80V
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9053
Operate delay
Variant
Auxiliary voltage
AC/DC 24 - 80 V
Contact equipping
2 changeover contacts
Measuring range
AC 1,5 - 15 A
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overcurrent relay. Energized on trip. Time delay at response value
The Dold current relay BA9053/010 AC1,5-15A AC/DC24-80V is an overcurrent relay of the VARIMETER series, designed for monitoring single-phase DC and AC power networks. It is used for continuous monitoring of the current consumption of electrical loads to detect deviations from normal operation at an early stage. The device setting is performed via rotary switches on the front, ensuring simple and user-friendly configuration. The relay operates on the operating current principle and is suitable for use in industrial and railway applications.
Applications
This relay is intended for use in industrial plants and rail transport, where reliable current monitoring is required to prevent failures and ensure operational safety. It monitors the current consumption of loads such as motors, heaters, or electronic devices and can trigger a response when a set threshold is exceeded. The device is installed in enclosures, with a width of 45 mm enabling compact mounting in standard control panels.
Functions and Equipment in Detail
The device features 2 changeover contacts as output contacts, which are galvanically isolated from the measuring circuit. This ensures safe separation between the measuring and auxiliary circuits, which is crucial for electrical safety. The measuring ranges cover AC 1.5 to 15 A, with the devices calibrated for sinusoidal AC currents in RMS value. Measurement is performed using the arithmetic mean of the rectified measuring current. The setting of the pickup value and hysteresis is done via the rotary switches on the front. The hysteresis depends on the set pickup value, ensuring stable switching behavior during minor fluctuations.
Technology Explained Simply
The relay operates as an overcurrent relay, but can also be used as an undercurrent relay, depending on requirements. The switching delay tv is 0 to 20 seconds and is activated once the set threshold is exceeded. This prevents unwanted tripping during short-term current peaks, such as during motor start-up. The pickup delay is also integrated, enabling controlled response to current changes. The auxiliary voltage can be operated in both AC and AC/DC mode with 24 to 80 V, allowing flexible integration into existing control systems.
Compatibility and Accessories
The relay is compliant with IEC/EN 60255-1 and IEC/EN 60947-1 standards and carries the approvals UKCA and CCC. It is designed for use in enclosures and can be mounted in standard plug-in rails. The terminal connections are clearly labeled: A1/A2 for auxiliary voltage, i/k for current input, and contacts 11-14 and 21-24 for the two changeover contacts. The LED indicators (green for operational readiness, yellow for activated output relay) enable visual monitoring of the operating status.
Mounting and Installation
Mounting is done in an enclosure, with a width of 45 mm allowing standard installation in DIN plug-in rails. The terminal connections are designed for connection with wires, with maximum permissible currents and voltages to be observed according to the technical data. The setting is performed on-site via the rotary switches on the front, without requiring additional tools or software.
Advantages in Operation
Early detection of current anomalies enables preventive maintenance, reducing failures and downtime. Precise and reliable measurement, along with galvanic isolation, increases operational safety. The integrated switching delay prevents false tripping during short-term load peaks, further improving operational safety. The LED indicators provide a quick visual overview of the operating status, accelerating fault localization.