| Technical data |
| 1- / 2-channel | 1, 2 |
| Approvals | UL-Recognized |
| Cat. / PL acc. to EN ISO 13849-1 | 4/e |
| Connection | Pluggable screw terminals |
| Output contacts max. | 1 NC contact, 5 NO contacts |
| SIL CL acc. to IEC/EN 62061 | 3 |
| SIL acc. to IEC/EN 62061 | 3 |
| Thermal current Ith max. | 5 A |
| Width | 22,5 mm |
| Type | BG 5929 |
| Variant |
| Contact equipping | 3 NO contacts, 2 NC contacts for feedback and signal circuit |
| Nominal voltage | AC/DC 24 V |
| Approvals and Markings | TÜV |
| Variant | For 2-channel connections |
The Dold expansion module BG5929.48/100 AC/DC24V is a safety relay for use in industrial control systems, particularly for safe contact multiplication and amplification of safety modules. It is used in installations where more safety circuits are required than a single safety module can provide. The device is designed for 1- and 2-channel wiring and features forced-guided contacts that ensure safe signal transmission. The contact configuration includes 3 normally closed contacts and 2 normally open contacts, with the normally open contacts specifically intended for feedback and alarm circuits. The rated voltage is AC/DC 24 V, making it suitable for standard applications in automation technology.
Applications
The expansion module is used in safety-critical applications, for example in combustion systems according to EN 50156-1. It is designed for use in systems certified up to Category 4 and Performance Level e according to EN ISO 13849-1, as well as up to SIL 3 according to IEC/EN 62061 and EN 61508. These certifications make it suitable for installations with high requirements for fault tolerance and reliability. The operational status indicator enables visual monitoring of the module during operation.
Functions and Equipment in Detail
The module offers a maximum output contact configuration of 5 normally closed contacts or a combination of 4 normally closed and 1 normally open contact, with one normally open contact specifically designated for the feedback circuit. The contacts are forced-guided, meaning they are mechanically designed so that one contact cannot close when another is open – a key feature for safety in critical installations. The connection technology uses removable screw terminals, enabling flexible and secure wiring. The width is 22.5 mm, making it suitable for standard control panels.
Technology Explained Simply
The forced guidance of contacts ensures that electrical connections cannot be unintentionally established in the event of a fault. This is crucial to avoid false alarms or hazardous conditions. The maximum thermal current rating (Ith) is 5 A, defining the electrical load capacity of the module. The TÜV and UL-Recognized certifications confirm compliance with international safety standards. The operational status indicator visually signals the module’s state, which is helpful during commissioning and maintenance.
Compatibility and Accessories
The expansion module is designed for use in conjunction with suitable switching devices and controls. It is used in combination with safety modules to increase the number of available safety contacts. Compatibility with 1- and 2-channel systems allows flexible integration into existing installations.
Mounting and Installation
Mounting is done in standard control panels with a width of 22.5 mm. The removable screw terminals simplify installation and maintenance, as they can be removed and repositioned without tools. The installation instructions are included in the manufacturer’s datasheet, which serves as the operating manual.
Operational Advantages
Using the BG5929.48/100 AC/DC24V enables safe and reliable expansion of contact count in safety systems. The certifications according to EN ISO 13849-1 and IEC/EN 62061 ensure compliance with required safety standards. The operational status indicator and removable terminals support maintenance and servicing. The construction with forced-guided contacts reduces the risk of false alarms and increases system reliability.
Safety Technical Data
The module meets the requirements for safety functions according to EN ISO 13849-1 (Category 4, PL e) and IEC/EN 62061 (SIL 3). These certifications are essential for use in installations with high safety requirements. The construction with forced-guided contacts and monitoring of the feedback circuit ensures high fault tolerance and reliability.
Certifications and Markings
The device carries TÜV and UL-Recognized certifications, confirming compliance with European and American safety standards. The certification according to EN 50156-1 makes it suitable for use in combustion systems. Marking is done in accordance with applicable standards for safety relays.
Operational Status Indicator
The integrated operational status indicator enables visual monitoring of the module. It signals whether the device is active or if a fault is present. This function is particularly useful during commissioning and maintenance, as it enables quick diagnosis.
Certifications and Markings
The device is equipped with TÜV and UL-Recognized certifications. It meets the requirements according to EN ISO 13849-1 (Category 4, PL e), IEC/EN 62061 (SIL 3), and EN 50156-1. These certifications confirm the safety and reliability of the module in critical applications.
Operational Status Indicator
The integrated operational status indicator enables visual monitoring of the module. It signals whether the device is active or if a fault is present. This function is particularly useful during commissioning and maintenance, as it enables quick diagnosis.