Further information for Dold 0053805 insulation monitor DC12-280V 5-200kOhm
Technical data
Enclosure design
Distribution board
IMD type
DC
Nominal voltage IT system
DC 12 - 280 V, DC 24 - 500 V
Response value
5 - 500 kΩ
Response value type
Adjustable
Width
35 mm
Type
IL 5881
Earth fault indicator
Variant
Alarm value
5 - 200 kOhm
Auxiliary voltage
Without
Contact equipping
2 changeover contacts
Nominal voltage
DC 12 - 280 V
Time delay
without
Approvals and Markings
UKCA, CCC
The insulation monitor IL5881.12/100 from Dold is a device for monitoring the insulation resistance in ungrounded DC networks (IT systems) with a nominal voltage of DC 12 to 280 V. It is designed for early detection of earth faults to ensure preventive fire and system protection, particularly in industrial applications and railway systems. Operational readiness is indicated by a green LED, while red LEDs signal earth faults on L+ or L-. The trip threshold is adjustable via a potentiometer on the front of the device and ranges from 5 to 200 kΩ.
Applications
The IL5881.12/100 is designed for use in industrial and railway applications, where the reliability of electrical supply is of high importance. It monitors IT systems, where the supply voltage is not directly grounded, to trigger an alarm message promptly in case of insulation failure. The selective earth fault detection for L+ and L- enables quick fault localization, thereby reducing maintenance time. The device is used in installation and industrial distributors according to DIN 43880.
Functions and Equipment in Detail
The device features two changeover contacts as contact configuration, which drop out in the event of a fault (rest current principle). The alarm message is indicated by red LEDs “RE+” and “RE-”, with the respective illuminated LED indicating the side of the earth fault (L+ or L-). The trip threshold is adjusted via a potentiometer on the front, allowing user-friendly adaptation to specific requirements. Activation of the internal test button “Test” simulates an earth fault to check the device’s functionality. An internal reset and test button is also provided.
Technology Explained Simply
The insulation monitor operates on the principle of continuous measurement of the insulation resistance between conductors L+ and L- relative to ground. When the resistance drops below the set alarm threshold of 5 to 200 kΩ, the fault is indicated by the corresponding LED and the output relay switches off. The function can be programmable to memory or hysteresis behavior. With hysteresis behavior, the device automatically resets when the insulation resistance rises above the alarm threshold again. With memory behavior, the fault condition remains stored until reset via internal or external reset function. An external reset and test button can be connected to enable operation from outside.
Compatibility and Accessories
The device is manufactured in the IL 5881 form factor, with a width of 35 mm and a depth of 61 mm. The connection terminals are located at the bottom, enabling installation in installation and industrial distributors according to DIN 43880. Mounting is possible either on DIN rail or by screws. The device holds UKCA and CCC certifications and complies with the requirements of standard IEC/EN 61557-8. A variant with separate auxiliary voltage is available for higher voltages up to DC 500 V, but is not part of this version.
Mounting and Installation
Mounting is carried out in distributors or enclosures, with DIN rail or screw mounting facilitating integration into existing systems. The connection terminals are intended for connection to the monitored IT system (L+, L-, PE) as well as for external test and reset functions (PT, LT). Terminal designations are clearly defined: A1 for L+, A2 for L-, PE for the protective conductor, PT/X1 for the external test button, and LT/X1 for the external reset function.
Advantages in Operation
The IL5881.12/100 offers reliable and simple monitoring of IT systems. The adjustable alarm threshold allows adaptation to different requirements, while selective indication precisely locates the fault. Integrated test and reset functions reduce maintenance time, and DIN rail mounting simplifies installation. The device is designed for use in industrial environments where high operational safety is required. Operational readiness is indicated by the green LED, making the device’s status always visible.