Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Nominal voltage max.
AC 1000 V, DC 900 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9054
Operate delay
Variant
Auxiliary voltage
AC/DC 80 - 230 V
Contact equipping
2 changeover contacts
Measuring range
AC 50 - 500 V
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Undervoltage relay. De-energized on trip. Time delay at hysteresis value
The Dold voltage relay BA9054/012AC50-500VAC/DC80-230V is an industrial device for monitoring single-phase DC and AC voltage networks. It is used for continuous monitoring of the network voltage to detect voltage drops or overvoltages early and thus prevent failures in electrical systems. The device operates on the principle of rest current and is configured as an undervoltage relay, with the switching delay activated upon reaching the hysteresis value. Adjustment is performed via rotary switches on the device front, enabling user-friendly and precise adaptation to specific requirements.
Applications
This relay is suitable for use in industrial and railway applications where high operational safety and reliability of electrical systems are required. It monitors voltages in the range of AC 50 to 500 V and can be used both as an undervoltage relay and as an overvoltage relay, with the function determined by the setting of the threshold values. The galvanic isolation between the auxiliary circuit and the measurement circuit ensures safe and interference-free measurement, even at high voltages.
Functions and Equipment in Detail
The device features two changeover contacts, which can be used to control auxiliary circuits or alarm systems. The contact position is indicated by LED displays: a green LED indicates operational readiness, while a yellow LED indicates activation of the output relay. The switching delay ranges from 0 to 20 seconds and is designed to ignore short-term voltage fluctuations, triggering a response only in case of sustained faults. The pickup delay is also integrated to allow a delayed response upon reaching the set value.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measurement voltage. For AC voltages, the device is calibrated to the RMS value, enabling accurate measurement even with sinusoidal voltages. The auxiliary voltage can be supplied in AC or AC/DC operation (80–230 V), allowing flexible integration into existing power supply systems. The maximum rated voltage is AC 1000 V and DC 900 V, with measurement ranges adjusted according to the variant. The width of 45 mm allows for compact mounting in enclosures.
Compatibility and Accessories
The relay is designed for use in industrial enclosures and complies with standards IEC/EN 60255-1 and IEC/EN 60947-1. It is certified with approvals such as UKCA and CCC, enabling use in various markets. The galvanic isolation between the measurement and auxiliary circuits ensures safe and interference-free operation. The terminal connections are clearly labeled: A1/A2 for auxiliary voltage, e/f for voltage input, and 11/12/14 as well as 21/22/24 for the two changeover contacts.
Mounting and Installation
Mounting is performed in an enclosure, with the width of 45 mm enabling standard installation in DIN housings. Adjustment of the threshold values and hysteresis is done via rotary switches on the front of the device. The terminal connections are clearly labeled, ensuring error-free wiring. The LED indicators support commissioning and maintenance by visually displaying the operational status.
Advantages in Operation
By detecting voltage anomalies early, the relay enables preventive maintenance and reduces the likelihood of system failures. The switching delay and pickup delay prevent unnecessary switching operations during short-term disturbances. Galvanic isolation increases safety and prevents interference in the auxiliary circuit. The clear LED indication simplifies diagnosis and maintenance of the device during operation.