Further information for Dold 0053708 voltage relay AC5-50V UH AC/DC24-80V
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Nominal voltage max.
AC 1000 V, DC 900 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9054
Operate delay
Variant
Auxiliary voltage
AC/DC 24 - 80 V
Contact equipping
2 changeover contacts
Measuring range
AC 5 - 50 V
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Undervoltage relay. De-energized on trip. Time delay at hysteresis value
The voltage relay BA9054/012 from Dold is an industrial device for monitoring single-phase AC networks in the range of AC 5 to 50 V. It functions as an undervoltage relay and operates on the principle of rest current, with switching delay activated upon reaching the hysteresis value. The device is designed for use in enclosures and has a width of 45 mm, making it suitable for standard control panels. Device settings are adjusted via rotary switches on the front, ensuring simple and user-friendly configuration.
Applications
This relay is intended for monitoring DC and AC voltages in industrial plants as well as in railway applications. It enables early detection of voltage deviations to prevent electrical system failures and enhance operational safety. Preventive maintenance is supported by its fault localization capability, thereby increasing productivity and improving system availability.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which can be used to control auxiliary circuits. The auxiliary voltage is AC/DC 24 to 80 V, allowing flexible use in various networks. The switching delay can be set between 0 and 20 seconds, enabling controlled response to voltage fluctuations. The pickup delay is also integrated to avoid unwanted switching operations during short-term voltage variations.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measured voltage. For AC voltages, the device is calibrated to the RMS value. Settings are adjusted via rotary switches, allowing manual adjustment of both the pickup value and the hysteresis value. The hysteresis depends on the set pickup value, ensuring stable switching behavior. Galvanic isolation between the measuring circuit and auxiliary circuit ensures safe insulation and prevents interference in the control circuit.
Compatibility and Accessories
The relay complies with standards IEC/EN 60255-1 and IEC/EN 60947-1. It is designed for measuring frequencies up to 5 kHz and features high overload capacity. The maximum permissible continuous voltage is AC 1000 V and DC 900 V. The terminal connections are clearly labeled: A1/A2 for auxiliary voltage, e/f for voltage input, and contacts 11-14 and 21-24 for the two changeover contacts. LED indicators (green for operational readiness, yellow for activated output relay) allow visual monitoring of the operating status.
Mounting and Installation
The device is mounted in enclosures and is designed for installation on 35 mm rails. The terminal connections are intended for cable connections, with labeling enabling clear assignment. Settings are adjusted directly on the front panel without requiring additional tools or software.
Advantages in Operation
Precise and reliable measurement, combined with integrated switching delay, increases the reliability of the monitored system. LED indicators simplify diagnostics during operation, and galvanic isolation enhances safety. The relay protects against device damage due to overvoltage and enables rapid fault localization, reducing maintenance time. Compliance with international standards ensures safe and standardized integration into existing systems.