Further information for Dold 0053684 voltage relay AC25-250V AC/DC80-230V
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Nominal voltage max.
AC 1000 V, DC 900 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9054
Operate delay
Variant
Auxiliary voltage
AC/DC 80 - 230 V
Contact equipping
2 changeover contacts
Measuring range
AC 25 - 250 V
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overvoltage relay. De-energized on trip. Time delay at setting value
The Dold voltage relay BA9054/011 is an overvoltage relay of the VARIMETER series, designed for monitoring single-phase DC and AC voltage networks. It serves for the early detection of voltage anomalies to prevent damage to electrical installations and enhance operational safety. Device settings are adjusted via rotary switches on the front panel, ensuring simple and user-friendly configuration. The device operates on the standby current principle, where contacts are closed in the normal state and open when the set threshold value is exceeded.
Applications
This relay is suitable for use in industrial plants as well as in railway applications. It monitors voltages in the range of AC 25 to 250 V and can be used as both an overvoltage and undervoltage relay, with hysteresis depending on the set value. Galvanic isolation between the measurement circuit and auxiliary circuit ensures safe and interference-free measurement.
Functions and Features in Detail
The device features 2 changeover contacts as output contacts, which can be used to control auxiliary circuits or alarm systems. The switching delay is 0 to 20 seconds and is activated once the set threshold is exceeded. This enables controlled response to short-term voltage spikes, avoiding false tripping. The response delay is also integrated to control the reaction to voltage changes. The start-up bypass is not available in this variant.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measurement voltage. For AC voltages, the device is calibrated to the RMS value. Settings are adjusted via rotary switches, allowing both the pickup value and the drop-out value (hysteresis) to be set. The auxiliary voltage is supplied in the range of AC/DC 80 to 230 V, enabling connection to various supply voltages. The maximum rated voltage is AC 1000 V and DC 900 V, with measurement ranges varying depending on the variant.
Compatibility and Accessories
The device complies with standards IEC/EN 60255-1 and IEC/EN 60947-1. It is designed for use in enclosures and has a width of 45 mm. LED indicators signal operational readiness (green LED) and activation of the output relay (yellow LED). Terminal markings follow A1/A2 for auxiliary voltage, e/f for measurement connection, and 11/12/14 as well as 21/22/24 for the two changeover contacts.
Mounting and Installation
Mounting is carried out in standard enclosures. Connection terminals are clearly labeled, ensuring error-free installation. Devices are designed for vertical mounting, with electrical connections to be made according to technical data and manufacturer’s circuit diagrams.
Operational Advantages
Precise and reliable measurement, combined with integrated switching delay, increases the reliability of the monitored system. Early fault detection enables preventive maintenance, reducing downtime and increasing productivity. Galvanic isolation between measurement and auxiliary circuits protects electronic components from interference and enhances system safety.