Further information for Dold 0053639 voltage relay AC230V
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Nominal voltage max.
AC 1000 V, DC 900 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9054
Operate delay
Variant
Auxiliary voltage
AC 230 V
Contact equipping
2 changeover contacts
Measuring range
AC 25 - 250 V
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overvoltage relay. Energized on trip. Time delay at setting value
The Dold voltage relay BA9054/010AC25-250VUHAC230V is an industrial-grade overvoltage relay from the VARIMETER series, designed for monitoring single-phase DC and AC voltage networks. It enables early detection of voltage anomalies to prevent damage to electrical installations and enhance operational safety. Device settings are adjusted via rotary switches on the front panel, ensuring simple and user-friendly configuration. The relay operates on the principle of operating current and switches when the set threshold is exceeded, with an integrated switching delay of 0 to 20 seconds. The auxiliary voltage is AC 230 V, and the measured voltage is monitored in the range of AC 25 to 250 V. The output contacts consist of two changeover contacts suitable for controlling auxiliary circuits.
Applications
This relay is intended for use in industrial and railway applications where reliable voltage monitoring is required. It is particularly suitable for installations that need protection against overvoltage to avoid equipment damage. The galvanic isolation between the measurement circuit and auxiliary circuit ensures safe and interference-free signal transmission. The device is installed in enclosures, with a width of 45 mm enabling compact mounting.
Functions and Equipment in Detail
The device measures the arithmetic mean of the rectified measured voltage and is calibrated for sinusoidal AC voltages based on RMS value. Settings are adjusted via a rotary switch, allowing both the pickup value and the drop-out value (hysteresis) to be configured. The hysteresis depends on the set value and ensures stable switching behavior. The switching delay t_v delays switching after exceeding the threshold, which is effective in overvoltage relays upon reaching the set value. The start-up bypass feature is not available in this variant. LED indicators signal operational readiness (green LED) and activation of the output relay (yellow LED).
Technology Explained Simply
Measurement is performed via terminals e and f, with a measurement range of AC 25 to 250 V. The auxiliary voltage is supplied via terminals A1 and A2. The output contacts (11-14, 21-24) are configured as changeover contacts, enabling control of auxiliary circuits. The maximum rated voltage is AC 1000 V and DC 900 V. Galvanic isolation between the measurement and auxiliary circuits prevents interference and enhances safety. The measurement frequency can reach up to 5 kHz, making it suitable for dynamic applications. The pickup delay is activated, meaning the relay does not respond immediately but includes a short delay to filter out brief voltage fluctuations.
Compatibility and Accessories
The relay is designed for use in single-phase systems and can be employed as either an overvoltage or undervoltage relay. It complies with standards IEC/EN 60255-1 and IEC/EN 60947-1, ensuring reliability and safety in industrial environments. Certifications UKCA and CCC are available, enabling use in respective markets.
Mounting and Installation
Mounting is performed in enclosures, with a width of 45 mm allowing standard installation. The connection terminals are clearly labeled (A1/A2 for auxiliary voltage, e/f for measured voltage, 11-14 and 21-24 for changeover contacts), ensuring easy installation. Settings are adjusted via rotary switches on the front panel, requiring no additional tools. The LED indicators support commissioning and maintenance by visually displaying the operational status.
Operational Advantages
The relay enables preventive maintenance by detecting voltage anomalies early, preventing failures and increasing productivity. Precise and reliable measurement, along with galvanic isolation, ensures high operational safety. The switching delay reduces false tripping caused by brief voltage fluctuations. The LED indicators simplify diagnosis and fault localization. Compliance with standards IEC/EN 60255-1 and IEC/EN 60947-1, as well as UKCA and CCC certifications, guarantees suitability for industrial applications.