Further information for Dold 0053379 IL5880.12 insulation monitor 380-415V
Technical data
Enclosure design
Distribution board
IMD type
AC
Nominal voltage IT system
AC 0 - 500 V
Response value
5 - 500 kΩ
Response value type
Adjustable
Width
35 mm
Type
IL 5880
Earth fault indicator
Variant
Alarm value
5 - 100 kOhm
Auxiliary voltage
AC 380- 415 V 50 - 400 Hz
Contact equipping
2 changeover contacts
Prewarning value
Without
Approvals and Markings
UKCA, CCC
Variant
Adjustable alarm value. De-energized on trip
The IL5880.12 insulation monitor from Dold is a device for monitoring insulation resistance in ungrounded AC and three-phase networks (IT systems) with a rated voltage of AC 0 to 500 V. It is designed for early detection of earth fault conditions to ensure preventive fire and plant protection. The device operates on the idle current principle, whereby the output relay is not activated in the event of a fault, enabling safe and reliable signaling. The auxiliary voltage is AC 380–415 V at a frequency of 50–400 Hz, allowing monitoring of de-energized systems as well.
Applications
The IL5880.12 is designed for pure AC and three-phase networks operating in the range of 0 to 500 V and 10 to 10000 Hz. It is used in industrial and railway applications, as well as in systems requiring continuous monitoring of insulation resistance. The separate supply voltage enables monitoring even when the network is de-energized, which is advantageous for emergency or backup systems. The IL5880.12 variant is specifically designed for monitoring IT systems that do not have a direct earth connection.
Functions and Equipment in Detail
The device features two changeover contacts for signaling faults. The trip threshold for earth fault is adjustable via a potentiometer on the front panel and ranges from 5 to 100 kΩ. Indication is provided by LEDs: a green LED indicates operational readiness, while a red LED signals an earth fault. The function of the output relays is programmable, allowing selection between memory and hysteresis behavior. An integrated reset and test button is provided, and additional external buttons can be connected.
Technology Explained Simply
The insulation monitor checks the resistance between the electrical system and earth. If the insulation resistance drops below the set alarm threshold of 5 to 100 kΩ, a fault is signaled. Galvanic isolation between the measurement circuit, auxiliary voltage, and output contacts ensures high safety. Adjustment is user-friendly via a potentiometer, allowing the alarm threshold to be individually adapted to the requirements of the installation. The operating voltage is supplied via the auxiliary voltage (AC 380–415 V), which is independent of the monitored network.
Compatibility and Accessories
The device is specified according to IEC/EN 61557-8 and meets the requirements for monitoring IT systems. It is designed for mounting in installation and industrial distributors according to DIN 43880. The width is 35 mm, and mounting is either on a DIN rail or by screws. The housing design is intended for installation distributors.
Mounting and Installation
Mounting is in standard installation distributors with a depth of 61 mm. The connection terminals are located at the bottom of the device, facilitating integration into existing control panels. DIN rail or screw mounting allows flexible installation. Terminal markings include connections for the monitored IT network (L, N), protective earth (PE), external test and reset buttons (PT, LT1, LT2), and output contacts (11, 12, 14, 21, 22, 24). Installation is carried out according to the manufacturer’s technical instructions.
Advantages in Operation
The IL5880.12 provides reliable and early detection of insulation faults, increasing plant safety. The simple adjustment of the trip threshold and clear LED indication simplify maintenance. Galvanic isolation and the idle current principle ensure safe operation. The ability to connect external buttons enables flexible integration into existing monitoring systems. Compliance with the IEC/EN 61557-8 standard ensures conformity with international standards.