Dold 0053182, EAN: 4030641531829

Dold 0053182 current relay BA9053/012 AC230V

Dold 0053182 current relay BA9053/012 AC230V

Lieske Part No. 1153614
Mfg Part No 0053182
EAN-Code 4030641531829
Manufacturer Dold
Here only 255,64 EUR
304,21 EUR incl. VAT

Further information for Dold 0053182 current relay BA9053/012 AC230V

Technical data
1- / 3-phase1
Enclosure designSwitch cabinet
Output contacts2 C/O contacts
Width45 mm
TypeBA 9053
Operate delayYes
Variant
Auxiliary voltageAC 230 V
Contact equipping2 changeover contacts
Measuring rangeAC 0,1 - 1 A
Start up delayWithout
Switching delay0 - 20 s
Approvals and MarkingsUKCA, CCC
VariantUndercurrent relay. De-energized on trip. Time delay at hysteresis value
The Dold current relay BA9053/012 is an undercurrent relay of the VARIMETER series, designed for monitoring single-phase AC networks. It operates on the residual current principle and is designed for use in enclosures. Device settings are adjusted via rotary switches on the front, enabling simple and user-friendly configuration. The relay monitors current flow in electrical installations and is used for early detection of deviations to prevent failures and enhance operational safety.

Applications
This relay is suitable for monitoring current consumption of electrical consumers in industrial and railway applications. It can be used in systems requiring continuous current monitoring to detect malfunctions or power outages early. Applications are particularly in installations where interruption of current flow is critical, such as in production plants or rail vehicle technology.

Functions and Equipment in Detail
The device features two changeover contacts as output contacts, used for controlling external circuits. The measurement ranges are from AC 0.1 to 1 A, with the devices calibrated for sinusoidal AC currents in RMS value. The switching delay is 0 to 20 seconds and is activated when the hysteresis threshold is undershot. The pickup delay is also integrated, enabling precise response to current changes. The auxiliary voltage is AC 230 V, allowing supply via standard mains voltage. There is no start-up bypass, so no special deactivation occurs during inrush currents.

Technology Explained Simply
The relay measures the arithmetic mean of the rectified measured current. Galvanic isolation between the auxiliary circuit and the measurement circuit ensures safe and interference-free measurement. The LED indicator shows operational readiness (green LED) and activation of the output relay (yellow LED). Settings are adjusted via rotary switches, allowing manual adjustment of the pickup value and hysteresis value. The hysteresis depends on the set pickup value, ensuring stable switching behavior.

Compatibility and Accessories
The relay is designed for use in single-phase systems and can be configured as either an overcurrent or undercurrent relay. It is manufactured according to standards IEC/EN 60255-1 and IEC/EN 60947-1. UKCA and CCC approvals are available, enabling use in respective markets. The width is 45 mm, allowing installation in standard enclosures. The measurement frequency can reach up to 5 kHz, enabling detection of rapidly changing current signals.

Mounting and Installation
Mounting is done in enclosures using the provided mounting elements. The connection terminals are clearly labeled: A1 and A2 for auxiliary voltage, i and k for current input, and contacts 11, 12, 14 and 21, 22, 24 for the two changeover contacts. Installation requires no special tools, as settings are adjusted via rotary switches on the front. The auxiliary voltage is supplied via AC 230 V, making integration into existing power supply systems straightforward.

Operational Advantages
Precise and reliable current monitoring enables preventive maintenance and reduces the likelihood of system failures. Rapid fault localization via LED indicator and switching delay enhances operational safety. Galvanic isolation between measurement and auxiliary circuits protects the installation from interference. Simple operation via rotary switches reduces installation time and maintenance effort. The width of 45 mm allows compact installation in existing enclosures without requiring additional space.