Further information for Dold 0053159 current relay BA9053/011 AC0,5-5A AC230V 0-20S
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9053
Operate delay
Variant
Auxiliary voltage
AC 230 V
Contact equipping
2 changeover contacts
Measuring range
AC 0,5 - 5 A
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overcurrent relay. De-energized on trip. Time delay at response value
The Dold current relay BA9053/011 is an overcurrent relay of the VARIMETER series, designed for monitoring single-phase AC circuits. It operates on the rest current principle, where the contacts are closed during normal operation and only open when the set current value is exceeded. The device setting is adjusted via a rotary switch on the front panel, enabling simple and user-friendly adjustment of the pickup value. The relay is designed for use in enclosures and has a width of 45 mm, making it suitable for standard control panels.
Applications
This relay is used for continuous monitoring of current consumption in electrical loads within industrial plants and railway applications. It enables early detection of overcurrent conditions, supporting preventive maintenance and preventing electrical system failures. The application is particularly suited for systems requiring high operational safety and reliability.
Functions and Equipment in Detail
The device monitors current in the range of AC 0.5 to 5 A. Measurement is performed using the arithmetic mean of the rectified measured current, with the devices calibrated for sinusoidal AC currents in RMS value. The switching delay is 0 to 20 seconds and is activated once the set threshold is exceeded. This delay prevents false alarms caused by short-term current surges. The pickup delay is also integrated to ensure precise response to current variations.
Technology Explained Simply
The auxiliary voltage is AC 230 V, allowing the relay to be operated in standard mains voltage installations. The output contacts consist of 2 changeover contacts, which are galvanically separated from the measurement circuit, ensuring safe isolation between the measurement and control circuits. The LED indicators signal the operating status: a green LED lights up when auxiliary voltage is applied, and a yellow LED indicates activation of the output relay. The devices comply with IEC/EN 60255-1 and IEC/EN 60947-1 standards and carry the approvals UKCA and CCC.
Compatibility and Accessories
The relay is designed for use in single-phase systems and can be used as either an overcurrent or undercurrent relay, with hysteresis depending on the set value. The terminal connections are clearly labeled: A1/A2 for auxiliary voltage, i/k for current input, and contacts 11-14 and 21-24 for the two changeover contacts. The measurement frequency can reach up to 5 kHz, enabling use in systems with high frequencies.
Mounting and Installation
Mounting is performed in enclosures using screw fastening. The terminals are designed for direct connection to wires. The pickup value is adjusted via the rotary switch on the front panel, with the reset value set via hysteresis. The devices are designed for high overload capacity, with maximum permissible current values varying depending on the measurement range.
Advantages in Operation
Precise and reliable current monitoring enables faster fault localization and contributes to higher productivity. The integrated switching delay reduces false alarms, especially during short-term current surges. The LED indicators provide visual feedback on the operating status, simplifying maintenance and diagnostics. The galvanic separation between auxiliary and measurement circuits enhances operational safety.