Further information for Dold 0053134 current relay AC0,5-5A AC/DC80-230V
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9053
Operate delay
Variant
Auxiliary voltage
AC/DC 80 - 230 V
Contact equipping
2 changeover contacts
Measuring range
AC 0,5 - 5 A
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overcurrent relay. Energized on trip. Time delay at response value
The Dold current relay BA9053/010 AC0,5-5A AC/DC80-230V is an overcurrent relay of the VARIMETER series, designed for monitoring single-phase DC and AC power networks. It is used for continuous monitoring of the current consumption of electrical loads to react promptly to deviations from the set value. Device settings are adjusted via rotary switches on the front panel, ensuring simple and user-friendly configuration. The device is intended for use in enclosures and has a width of 45 mm, allowing integration into standard enclosure formats.
Applications
This relay is intended for use in industrial and railway applications where high operational safety and reliability are required. It monitors the current consumption of motors, transformers, or other electrical loads to detect overloads or faults at an early stage. This supports preventive maintenance, as anomalies can be identified before a failure occurs. The devices are specified according to IEC/EN 60255-1 and IEC/EN 60947-1, confirming compliance with international standards for measuring and protective devices.
Functions and Equipment in Detail
The relay operates on the operating current principle and measures the arithmetic mean of the rectified measured current. For sinusoidal AC currents, it is calibrated to the RMS value. The measurement ranges cover AC 0.5 to 5 A, with the measurement circuit being galvanically separated from the auxiliary circuit. The auxiliary voltage is AC/DC 80 to 230 V, allowing flexible adaptation to various power supply networks. The output contacts consist of 2 changeover contacts, which can be used to control additional circuits or alarms.
Technology Explained Simply
The switching delay is 0 to 20 seconds and is activated when the set threshold value is exceeded. This prevents unwanted tripping during short-term current peaks, such as during motor start-up. The pickup delay is also integrated, ensuring controlled response to current changes. The hysteresis, i.e., the difference between pickup and drop-out values, depends on the set value and ensures stable switching behavior. Device indicators include a green LED, which lights up when operating voltage is applied, and a yellow LED, which indicates the activated output relay state.
Compatibility and Accessories
The relay is designed for use in single-phase systems and can be used as either an overcurrent or undercurrent relay, with the function determined by setting the threshold values. The galvanic separation between the measurement and auxiliary circuits increases safety and prevents interference in the control circuit. The maximum measurement frequency is 5 kHz, enabling use in applications with rapid current changes. The devices are designed for high overload capacity, with maximum permissible currents varying according to the measurement range.
Mounting and Installation
Mounting is performed in enclosures, with the 45 mm width ensuring compatibility with standard switchboards. The connection terminals are clearly labeled: A1/A2 for auxiliary voltage, i/k for current input, and contacts 11-14 and 21-24 for the two changeover contacts. Settings are adjusted via rotary switches on the front panel, allowing direct operation on the device. The devices are designed for industrial environments and comply with UKCA and CCC certifications.
Advantages in Operation
Early detection of current anomalies enables preventive maintenance and reduces the likelihood of failures. The clear LED indicators facilitate diagnosis during operation. The switching delay prevents false tripping during short-term load peaks, increasing reliability. The galvanic separation between the measurement and auxiliary circuits ensures safe and interference-free operation. Compliance with IEC/EN 60255-1 and IEC/EN 60947-1 standards guarantees the quality and safety of the device.