Further information for Dold 0053089 safety relay BH5903.03/00000 DC24V
Technical data
1- / 2-channel
1, 2
Approvals
UL
Cat. / PL acc. to EN ISO 13849-1
4/e
Connection
Pluggable screw terminals
Output contacts max.
3 NO contacts
SIL CL acc. to IEC/EN 62061
3
SIL acc. to IEC/EN 62061
3
Thermal current Ith max.
5 A
Width
45 mm
Type
BH 5903
Cross fault detection
Variant
Contact equipping
3 NO contacts
Nominal voltage
DC 24 V
Approvals and Markings
UL-listed C/US, TÜV, UKCA
Variant
Für 2-kanaligen Anschluß von einem Not-Aus-Taster
The Dold safety relay BH5903.03/00000 DC24V is a specialised emergency stop module for use in industrial plants, particularly in systems that automatically restart after power restoration following a power failure, such as in compressor controls or water and wastewater technology. The device is designed for 2-channel connection of an emergency stop pushbutton and provides a secure, redundant control of the emergency stop function. It features a contact configuration with 3 normally closed contacts and is rated for a nominal voltage of DC 24 V. The width is 45 mm, making it suitable for use in standard DIN control panels.
Applications
This safety relay is used in plants where safe shutdown upon emergency stop actuation and controlled restart after power failure are required. Typical applications include machine controls, pump units, compressors, and plants in wastewater and water supply. The automatic restart function upon power restoration — provided the emergency stop has not been activated — enables continuous operational readiness without manual reset. The feedback loop for external contact amplification extends its applicability in complex safety circuits.
Functions and Equipment in Detail
The device stores the actuation of an emergency stop pushbutton and activates the safety function accordingly. It detects cross-wiring as well as short circuits and wire breaks at all inputs, increasing the reliability of the safety function. LED indicators for channel 1 and channel 2, as well as for fault diagnosis, allow for quick visual inspection of the operating status. The connection technology uses removable screw terminals suitable for wires with 2 x 1.5 mm² (with ferrule and plastic sleeve DIN 46228-1/-2/-3/-4) or 2 x 2.5 mm² (with ferrule DIN 46228-1/-2/-3).
Technology Explained Simply
The safety relay operates according to industrial safety function standards. It meets the requirements of Performance Level (PL) e and Category 4 according to EN ISO 13849-1, ensuring high safety performance in critical applications. Additionally, it complies with the Safety Integrity Level (SIL CL) 3 according to IEC/EN 62061 and Safety Integrity Level (SIL 3) according to IEC/EN 61508. The maximum thermal current is 5 A, defining the load capacity of the output contacts. Cross-wiring detection ensures that a short circuit between inputs is recognised and the safety function responds accordingly.
Compatibility and Accessories
The module is designed for 2-channel connection of an emergency stop pushbutton. It can be used in combination with other safety components, especially in systems requiring a feedback loop for external contact amplification. Certifications UL-listed C/US, TÜV, and UKCA confirm compliance with international safety standards. The connection terminals are removable, facilitating installation and maintenance.
Mounting and Installation
The device is mounted in DIN control panels. The removable screw terminals allow for flexible and secure wiring. The terminals are designed for the specified wire cross-sections, with the use of ferrules and plastic sleeves DIN 46228-1/-2/-3/-4 recommended. The LED indicators support installation by providing visual status indication.
Operational Advantages
The automatic restart function upon power restoration reduces the need for manual reset and increases operational readiness. The integrated fault diagnosis via LED indicators enables quick identification of malfunctions. Cross-wiring detection, as well as short circuit and wire break detection, enhance the reliability of the safety circuit. Certifications according to UL, TÜV, and UKCA ensure compliance with international safety standards.