| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 1 C/O contact |
| Time function(s) | Off-delay, with control signal |
| Width | 22,5 mm |
| Type | BC 7933N |
| Variant |
| Contact equipping | 1 changeover contact |
| Nominal voltage | AC 110 - 240 V |
| Time range | 5 - 100 s |
| Variant | Release delay, with control signal |
The Dold time relay BC7933N.81 is a drop-out delayed industrial time relay for use in enclosures. It features a rated voltage of AC 110 to 240 V and an adjustable time range of 5 to 100 seconds. The function is specifically designed for applications where the output contact delays returning to its rest position after the control signal is switched off. The device is designed in accordance with the standard EN 61812-1 and is suitable for time-dependent controls in industrial installations.
Applications
This time relay is used in industrial control systems where a time-delayed reset of switching operations is required. Examples include delay during motor shutdown, ensuring cooling-down times in machines, or signal delay in automation systems. The width of 22.5 mm allows for compact mounting in standard control panels.
Functions and equipment in detail
The device features a
changeover contact as the output contact, rated for an operating voltage of AC 250 V. The contact material consists of
AgNi contact material, ensuring high switching capacity and long service life. The
LED indicator signals the state of the output relay – it lights up when contact 15–18 is closed. The time delay is
continuously adjustable and can be set within the range of 5 to 100 seconds. The reset time is less than 50 ms, enabling a quick return to the operating state.
Technology explained simply
The time relay requires a continuously applied operating voltage at terminals A1–A2. The control input B1 is operated at the rated voltage, eliminating the need for a potential-free control contact. The drop-out delay is determined by the time constant of the internal circuit, which is adjusted via a rotary knob. The minimum switching-on time is 15 ms for AC voltage, ensuring the relay responds correctly even to short control signals. The
voltage influence is less than 1 %, ensuring high stability of the time delay even with fluctuations in operating voltage.
Compatibility and accessories
The device is designed for operating voltages in the range of AC 110 to 240 V and can be operated in frequency ranges of 45 to 65 Hz. The terminal clamps allow connection of stranded wires with 2 x 1.5 mm² with sleeve and plastic collar according to DIN 46228-1/-2/-3/-4 or 2 x 2.5 mm² with sleeve according to DIN 46228-1/-2/-3. The
terminal designation is A1, A3, A2 for the operating voltage, B1, B3 for the control input, and 15, 16, 18 for the changeover contact. The
overvoltage category III and
pollution degree 2 make the device suitable for industrial environments.
Mounting and installation
The time relay is mounted in enclosures and is designed for continuous operation. Mounting is done via the designated terminals, with connection cross-sections and sleeves complying with DIN standards. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is from -25 °C to +70 °C. The maximum operating altitude is 2000 m above sea level.
Advantages in operation
The
drop-out delayed function enables controlled shutdown of loads, reducing mechanical stress. The
LED indicator provides visual feedback on the operating status. The
high mechanical life of 10⁸ switching operations and the
electrical life of 1.5 x 10⁵ switching operations at 1 A and AC 230 V ensure long service life. The
EMC tests according to IEC/EN 61000-4-2 to -4-6 and
radio interference suppression class B (EN 55011) ensure reliable operation in electromagnetically demanding environments.