Further information for Dold 0052325 IK9173.11/030 DC24V undervoltage relay
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Distribution board
Nominal voltage max.
AC 230 V, DC 125 V
Output contacts
1 C/O contact
Width
17,5 mm
Type
IK 9173
Operate delay
Variant
Contact equipping
1 changeover contact
Nominal voltage
DC 24 V
Response value
0,7 - 1,0 Un 4%
Time delay
0,5 - 20 s
Variant
NC circuit operation. Settable time delay t1. Settable response value
The Dold undervoltage relay type IK9173.11/030 DC24V 0,7-1,0UN4% is used for monitoring power networks for undervoltage conditions. It is part of the VARIMETER series and is employed in industrial installations as well as in railway applications, where reliable network monitoring is required. The device monitors single-phase AC power networks and detects deviations from the nominal voltage to respond promptly to potential failures. Measurement is carried out via the L-N voltage, with the arithmetic mean being recorded. The operational reliability and availability of the installation are enhanced through preventive maintenance and timely fault detection.
Applications
This relay is suitable for monitoring power supplies in industrial installations, enclosures, and railway applications. It can be used for automatic switching to a safety power supply or safety lighting in accordance with DIN VDE 0100-710 or DIN VDE 0108. Particularly in unstable networks, such as those with local power generation or in networks of the 2nd and 3rd world, the variant with time delay t2 is advantageous, allowing consumers to be switched back on in stages after a power failure. It is also suitable for machines that must not be restarted immediately after a short power interruption—for example, compressors.
Functions and Equipment in Detail
The device operates on the principle of residual current, where the output relay is not activated in the event of a fault. The contact configuration includes a changeover contact (11-12-14), which closes the 11-14 contact when an undervoltage is detected. The LED indicator signals the status of the output relay; the yellow LED lights up when the contact is activated. The pickup value is adjustable and ranges from 0.7 to 1.0 times the nominal voltage (Un), with a hysteresis of approximately 4%. The time delay t1 for fault signaling is adjustable between 0.5 and 20 seconds and is effective only as long as the phase voltage is at least 0.5 times the nominal voltage.
Technology Explained Simply
The nominal voltage is DC 24 V, although the device can also be operated with AC voltages up to 230 V and DC voltages up to 125 V. The maximum overload capacity is 1.15 times the nominal voltage. The response time of the input circuit during a phase failure is approximately 100 ms. The rated operating voltage of the output is AC 250 V, and the thermal current Ith is 4 A. The switching capacity according to AC 15 is 3 A for the make contact and 1 A for the break contact at AC 230 V. The electrical life is at least 300,000 switching operations at AC 230 V and 1 A (cos ϕ = 0.5). The mechanical life is specified as at least 30 million switching operations.
Compatibility and Accessories
The relay is designed for installation in installation and industrial distributors in accordance with DIN 43880. The IK 9173 housing type has a depth of 59 mm and bottom-mounted connection terminals. The width is 17.5 mm. It can operate without auxiliary voltage, reducing wiring effort. The devices comply with the standard IEC/EN 60255-1. The contact materials are made of AgNi, ensuring high switching durability and corrosion resistance. The maximum short-circuit withstand requires a fuse with 4 A gG/gL.
Mounting and Installation
The device is installed in standard installation distributors, with connection terminals located at the bottom. Mounting is carried out in DIN-standard distributors with a width of 17.5 mm. The connection terminals are designed for connection to L and N conductors. The operating temperature ranges from -20 °C to +60 °C, and the storage temperature ranges from -25 °C to +60 °C. The relative humidity is up to 93% at 40 °C, and the altitude is limited to a maximum of 2000 m.
Advantages in Operation
Early detection of undervoltage conditions and the ability to trigger fault signaling with time delay increase operational safety. Preventive maintenance enables higher productivity by avoiding costly damage from unexpected failures. Simple installation without auxiliary voltage reduces wiring effort. The LED indicator provides visual feedback on the relay’s status, simplifying fault diagnosis. Adjustable parameters such as pickup value and time delay allow application-specific adaptation of the device.