Further information for Dold 0051978 overvoltage relay 3AC400V

Technical data
1- / 3-phase1, 3
Auxiliary voltageWithout
Enclosure designDistribution board
Nominal voltage max.3/N AC 400 / 230 V
Output contacts1 C/O contact
Width17,5 mm
TypeIK 9170
Operate delayYes
Variant
Contact equipping1 changeover contact
Nominal voltage3AC 400 V
Response value0,9 - 1,3 Un
Time delay0,5 - 20 s
VariantWithout N. NO circuit operation. Settable time delay t1. Settable response value
The Dold overvoltage relay IK9170.11/033 is an industrial monitoring switch for three-phase power networks, specifically designed for detecting overvoltages. The device operates on the working current principle, where the output relay is activated in the event of a fault, and is rated for a nominal voltage of 3AC 400 V. It features an adjustable pickup value in the range of 0.9 to 1.3 times nominal voltage (Un) and allows for a time delay t1 for fault signaling in the range of 0.5 to 20 seconds. This variant is designed without a neutral conductor connection, making it suitable for applications in three-phase systems without an N conductor. The width is 17.5 mm, and the device is intended for mounting in installation and industrial distributors according to DIN 43880, with connection terminals located at the bottom.

Applications

The relay is used for continuous monitoring of three-phase power networks for overvoltages. It is suitable for both three-phase and single-phase connections, with phase sequence being arbitrary. The application is in industrial and installation environments where reliable voltage monitoring is required to prevent damage to connected devices or machinery. The devices are designed for continuous operation and can be used in environments with an operating temperature range of -20 to +60 °C.

Functions and Equipment in Detail

The device features a changeover contact as the output contact, consisting of a close contact (11-14) and an open contact (11-12). The contact materials are made of AgNi 0.15 + 0.3 μm Au, ensuring high switching durability and corrosion resistance. The rated operating voltage is AC 250 V, and the device can carry a thermal current of 4 A. The electrical life is at least 300,000 switching operations at AC 230 V and 1 A (cos ϕ = 0.5), and the mechanical life is at least 30 million switching operations. A yellow LED indicates the contact position – it lights up when the output relay contact is closed.

Technology Explained Simply

The relay monitors voltage in a three-phase network by measuring the arithmetic mean of each phase against the neutral conductor. In variants without a neutral conductor connection, L1 and L3 are measured against L2. The pickup value is adjustable, allowing the operator to adapt the threshold values to specific requirements. The hysteresis is approximately 4 % of the set pickup value, preventing switching operations due to minor voltage fluctuations. The time delay t1 enables delayed fault signaling, ignoring short-term voltage spikes. The device operates without auxiliary voltage, simplifying installation and ensuring independence from additional power supplies.

Compatibility and Accessories

The device is designed for mounting on a DIN rail according to IEC/EN 60715. The connection terminals are suitable for conductor cross-sections of 2 x 2.5 mm² solid or 2 x 1.5 mm² stranded wire with ferrules (DIN 46228-1/-2/-3/-4). The terminals are secured using flat terminals with self-lifting connection washers according to IEC/EN 60999-1. The device is available in two housing types: IK 9170 (59 mm depth, terminals at bottom) and SK 9170 (98 mm depth, terminals at top). The variant described here is the IK 9170.

Mounting and Installation

Mounting is done on a DIN rail, with the connection terminals located at the bottom. Conductor connections are made using flat terminals, secured with a tightening torque of 0.8 Nm. Terminal marking follows EN 50005. Installation is simple, as no auxiliary voltage is required. The devices are designed for use in installation and industrial distributors according to DIN 43880.

Advantages in Operation

The device provides reliable and low-maintenance voltage monitoring without additional power supply. Adjustable parameters such as pickup value and time delay allow flexible adaptation to different requirements. The LED indicator facilitates diagnosis of the operating status. The high mechanical and electrical life ensures long-term operation. The protection rating IP 40 for the housing and IP 20 for the terminals provide sufficient protection against dust and contact. EMC tests according to IEC/EN 61000-4-2 to -5 and radio interference suppression according to EN 55011 Class B ensure electromagnetic compatibility and immunity to interference.