| Technical data |
| 1- / 3-phase | 1, 3 |
| Auxiliary voltage | Without |
| Enclosure design | Distribution board |
| Nominal voltage max. | 3/N AC 400 / 230 V |
| Output contacts | 2 C/O contacts |
| Width | 35 mm |
| Type | IL 9079 |
| Variant |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | 3AC 500 V |
| Operate delay | 0,2 - 2 s |
| Reset value | 0,55 - 1,05 Un |
| Approvals and Markings | CCC |
| Variant | For 3p3w systems. Adjustable response value |
The Dold IL9079.12/0033AC500V0,55-1,05UN is an
undervoltage relay for monitoring three-phase power networks. It is designed to detect short-term voltage interruptions, such as those occurring during lightning strikes or switching operations in the network. In control systems, particularly in contactor and PLC systems, individual components may drop out during a brief interruption while others remain active, potentially leading to uncontrolled states. The relay generates an extended reset pulse from such short interruptions via an adjustable re-energizing delay, restoring the control system to a defined initial state and preventing erroneous automatic restarts.
Applications
This device is designed for use in industrial and installation distributors, particularly in systems requiring stable network voltage. It monitors three-phase networks at 3AC 500 V and is also suitable for single-phase connections. Applications include enclosures, control systems, and other electrical installations where a secure response to voltage failures is required. The design is intended for installation distributors according to DIN 43880, with bottom-mounted connection terminals and a width of 35 mm.
Functions and Features in Detail
The relay features
2 changeover contacts as output contacts, which drop out in the event of a fault. Voltage interruptions are detected if they last longer than 20 ms and the voltage drops below the set threshold. The
threshold value is adjustable between 0.55 and 1.05 times the nominal voltage (Un). The
re-energizing delay can be set between 0.2 and 2 seconds to generate a defined reset pulse. Status indication is provided by a green LED, which lights up when the network is fault-free. The device operates on the stand-by current principle, meaning the output relay is not activated during a fault. Phase sequence is irrelevant, and the device can operate without a neutral conductor connection.
Technical Explanation
Each phase voltage is measured against the neutral conductor. If at least one phase falls below the set threshold, the output relay drops out and the green LED turns off. The relay only re-energizes after all three phase voltages have risen above the pickup threshold, following the set delay time. The hysteresis is 4 % to prevent switching due to minor voltage fluctuations. The nominal frequency is 50/60 Hz, and the nominal power consumption is approximately 8 VA. The input resistances are specified at approximately 150 kΩ. The maximum overload capacity is 1.1 times the nominal voltage continuously.
Compatibility and Accessories
The device is designed for networks without a neutral conductor and can also be connected single-phase, requiring bridging of terminals L1, L2, and L3. It is rated for 3AC 500 V nominal voltage, with a maximum nominal voltage of 3/N AC 400 / 230 V. The devices are available in two housing types: IL 9079 with 59 mm depth and bottom-mounted terminals, and SL 9079 with 98 mm depth and top-mounted terminals. The connection terminals are designed for installation and industrial distributors according to DIN 43880.
Mounting and Installation
Mounting is performed in standard installation distributors with a width of 35 mm. The terminals are located at the bottom, enabling easy integration into existing distributors. The devices are suitable for use in enclosures with mounting plates and cable ducts. Installation requires no auxiliary voltage, as the device connects directly to the network being monitored.
Operational Advantages
The adjustable re-energizing delay ensures that all control components are synchronized and reset after an interruption, preventing uncontrolled states and enhancing operational safety. The green LED indicator allows for quick visual verification of the operating status. The fault memory configuration (re-energizing lockout) provides additional safety by preventing automatic restarts until a manual reset is performed. Compliance with IEC/EN 60255-1 ensures reliability and safety in industrial applications.