| Technical data |
| Classification | Temperaturüberwachung |
| Enclosure design | Distribution board |
| Measuring range max. | 250 °C |
| Output contacts | 1 C/O contact |
| Width | 17,5 mm |
| Type | IK 9094 |
| Variant |
| Auxiliary voltage | AC/DC 24 V |
| Contact equipping | 1 changeover contact |
| Response value | 0 - 150 C |
| Variant | Ohne galvanische Trennung zwischen Hilfs- und Messkreis. Einstellbare Hysterese 3 - 30 °C |
The temperature monitor IK9094.11AC/DC24V0-150C from Dold is an industrial monitoring relay of the VARIMETER series, specifically designed for continuous temperature monitoring in applications such as motors, ball bearings, or rooms. The device monitors temperature progression via a PT100 resistance thermometer input using 2-wire technology and reacts when the set threshold value is exceeded or in case of a broken wire in the sensor. This function enables early detection of faults to avoid costly failures and enhance operational safety.
Applications
This temperature monitor is intended for industrial applications, particularly for monitoring motors, bearings, rooms, and refrigeration systems. The stepless adjustment of the threshold value in the range of 0 to 150 °C allows flexible adaptation to different operating conditions. The devices are designed for use in installation and industrial distributors according to DIN 43880 and are suitable for systems requiring high availability and preventive maintenance.
Functions and Equipment in Detail
The device features an input for PT100 sensors, with a measurement current of approximately 2.5 mA. Temperature monitoring occurs in three independent ranges (0–50 °C, 50–100 °C, 100–150 °C), with the threshold value being steplessly adjustable within each range. The switching hysteresis is also steplessly adjustable and ranges from 3 to 30 °C. In case of a broken wire in the sensor, this is detected as an overtemperature, ensuring reliable fault detection. The LED indicator shows green for operational readiness and red when the threshold value is exceeded.
Technology Explained Simply
The temperature monitor operates on the principle of rest current, where the output relay drops out in the event of a fault. The auxiliary voltage is AC/DC 24 V, with voltage ranges for alternating current between 0.8 and 1.1 times the nominal voltage and for direct current between 0.9 and 1.25 times. The output contacts consist of a changeover contact, which can be used to control auxiliary functions such as alarms or shutdowns. Programming is done via terminal X1: connecting X1 to P0 activates hysteresis behavior, while no bridge results in memory behavior, where the fault message remains stored.
Compatibility and Accessories
The device is designed for PT100 sensors according to IEC/EN 60751. It is available in I form factor, featuring a depth of 59 mm and bottom-mounted connection terminals for installation distributors. The width is 17.5 mm, allowing mounting on DIN rail or via screws. The devices comply with the standard IEC/EN 60255-1. Variants with galvanic isolation between the measurement and auxiliary circuits, as well as threshold values down to –50 °C, are available, but not in this configuration.
Mounting and Installation
Mounting is done either on DIN rail or via screw fastening. The connection terminals are located at the bottom, facilitating integration into standard installation distributors according to DIN 43880. The depth of 59 mm and width of 17.5 mm allow for compact placement in enclosures. The devices are designed for use in industrial and railway applications.
Operational Advantages
Preventive maintenance is supported by early fault detection, increasing productivity and ensuring system availability. The LED indicator enables quick visual fault localization. The stepless adjustment of the threshold value and hysteresis offers flexibility in adapting to different requirements. Wire break detection ensures reliable monitoring even in case of mechanical damage to the sensor wiring system.