Dold 0051587, EAN: 4030641515874

Dold 0051587 IL9171.12/001 under-voltage relay 3AC400V

Dold 0051587 IL9171.12/001 under-voltage relay 3AC400V

Lieske Part No. 1002315
Mfg Part No 0051587
EAN-Code 4030641515874
Manufacturer Dold
Here only 153,30 EUR
182,43 EUR incl. VAT

Further information for Dold 0051587 IL9171.12/001 under-voltage relay 3AC400V

Technical data
1- / 3-phase1, 3
Auxiliary voltageWithout
Enclosure designDistribution board
Nominal voltage max.3/N AC 500 / 290 V
Output contacts2 C/O contacts
Width17,5 mm
TypeIL 9171
Operate delayYes
Variant
Contact equipping2 changeover contacts
Nominal voltage3AC 400 V
Response value0,55 - 1,05 Un
Time delaywithout
Approvals and MarkingsCCC
VariantWithout N. NC circuit operation. Without time delay. Settable response value
The Dold undervoltage relay IL9171.12/001 is an industrial monitoring switch for three-phase power networks, specifically designed for detecting undervoltage in 3-phase systems. It is used in installations where secure power supply is critical, for example, for automatic switching to a safety power supply or safety lighting in accordance with DIN VDE 0100-710 and DIN VDE 0108. The device operates on the rest current principle, whereby the output relay is not activated in the event of a fault, ensuring safe and reliable operation. The width is 17.5 mm, and it is designed for use in installation distributors, with connection terminals located at the bottom. The rated voltage is 3AC 400 V, and the pickup value is adjustable within a range of 0.55 to 1.05 times the rated voltage. This device variant is without neutral conductor connection and without time delay.

Applications
This relay is intended for monitoring three-phase networks for undervoltage and is particularly suitable for applications where a safe response is required in the event of voltage drop or phase failure. It can be used in both 3-phase and 1-phase networks; in single-phase operation, terminals L1, L2, and L3 must be bridged. Applications include network monitoring in industrial plants, buildings with emergency power supply, or systems requiring stable voltage. The variant without time delay is suitable for installations requiring immediate response to voltage drops.

Functions and Equipment in Detail
The device features 2 changeover contacts as output contacts, which can be used to control auxiliary circuits or switching operations. The LED indicator signals the contact position of the output relay — the yellow LED lights up when the relay is activated. Phase sequence is arbitrary, allowing flexible installation. The pickup value is adjustable, enabling adaptation to different network conditions. Monitoring is performed by measuring the arithmetic mean of the phase voltages; in variants without neutral conductor connection, L1 and L3 are measured against L2 (IK/SK 9171) or L1 and L2 against L3 (IL/SL 9171). The device operates without auxiliary voltage, simplifying installation and ensuring independence from additional power supplies.

Technology Explained Simply
The operation is based on continuous monitoring of the network voltage. When the set pickup value (0.55 to 1.05 Un) is undershot, the output contact switches, triggering a response in the connected system. The rest current principle means the relay is not activated during normal operation and only closes the contact in the event of a fault (e.g., undervoltage). Pickup delay is active, meaning the device initially enters the good state shortly after network connection, even if a fault exists, and only switches to the fault state after the delay time has elapsed. This prevents false alarms during brief voltage dips. The maximum rated voltage is 3/N AC 500 / 290 V, and the device is designed for frequencies between 45 and 65 Hz.

Compatibility and Accessories
The relay is designed for 3-phase networks but can also be connected in single-phase operation. It is available with either fixed or adjustable pickup value, with the variant described here featuring the adjustable pickup value. The devices are available in various designs, with the IL 9171 variant having a width of 17.5 mm and a depth of 59 mm. The devices are certified to IEC/EN 60255-1 and carry the CCC mark.

Mounting and Installation
Mounting is carried out in installation distributors in accordance with DIN 43 880. The connection terminals are located at the bottom, enabling easy integration into existing distributors. The width of 17.5 mm allows for compact placement. In single-phase applications, terminals L1, L2, and L3 must be connected together. The devices are designed for an operating voltage of 3AC 400 V, with an overload capacity of 1.15 times the rated voltage continuously. The frequency range of 45 to 65 Hz makes the device suitable for various network conditions.

Operational Advantages
The device provides reliable and independent network monitoring without auxiliary voltage. The adjustable pickup voltage allows flexible adaptation to different requirements. The LED indicator provides visual feedback on the operating status. The rest current principle reduces susceptibility to errors and increases safety. The compact design and suitability for installation distributors facilitate integration into existing systems. Certification to IEC/EN 60255-1 and the CCC mark guarantee compliance with international standards.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1002315
qrcode für Dold 0051587 IL9171.12/001 under-voltage relay 3AC400V