Dold 0050823, EAN: 4030641508234

Dold 0050823 IL9171.12 undervoltage relay 3/N AC400/230V

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Dold 0050823 IL9171.12 undervoltage relay 3/N AC400/230V

Lieske Part No. 362043
Mfg Part No 0050823
EAN-Code 4030641508234
Manufacturer Dold
Here only 159,43 EUR
189,72 EUR incl. VAT

Further information for Dold 0050823 IL9171.12 undervoltage relay 3/N AC400/230V

Technical data
1- / 3-phase1, 3
Auxiliary voltageWithout
Enclosure designDistribution board
Nominal voltage max.3/N AC 500 / 290 V
Output contacts2 C/O contacts
Width17,5 mm
TypeIL 9171
Operate delayYes
Variant
Contact equipping2 changeover contacts
Nominal voltage3/N AC 400 / 230 V
Response value0,55 - 1,05 Un
Time delaywithout
Approvals and MarkingsCCC
VariantWith N. NC circuit operation. Without time delay. Settable response value
The Dold undervoltage relay IL9171.12 is an industrial device for monitoring three-phase AC networks for undervoltage. It is used for network monitoring and enables switching to a safety power supply or safety lighting in accordance with DIN VDE 0100-710 or DIN VDE 0108. The device operates on the principle of rest current, whereby the output relay is not activated in the event of a fault, ensuring safe and reliable signal transmission. It is designed for mounting in installation distributors and has a width of 17.5 mm, enabling compact installation in standard distributors.

Applications
This relay is designed for monitoring 3-phase AC networks with a nominal voltage of 3/N AC 400/230 V. It can also be connected single-phase, in which case the terminals L1, L2, and L3 must be bridged. The application is particularly in industrial and commercial installations where continuous power supply is required for safety functions such as emergency lighting or emergency power units. Monitoring is independent of phase sequence, allowing flexible installation in existing networks.

Functions and Equipment in Detail
The device detects undervoltages in the network and responds with a pickup value of 0.55 to 1.05 times the nominal voltage. The contact configuration includes 2 changeover contacts, which can be used to control auxiliary functions or safety circuits. The LED indicator signals the contact position, with a yellow LED lighting up when the output relay is activated (contacts 11-14 closed). The hysteresis is approximately 4 %, ensuring stable switching behavior even with slight voltage fluctuations.

Technology Explained Simply
The relay measures the arithmetic mean of each phase against the neutral conductor (N). In variants without neutral conductor connection, the measurement is taken between L1 and L3 against L2 (IK/SK 9171) or between L1 and L2 against L3 (IL/SL 9171). The nominal voltage is 3/N AC 400/230 V, with a maximum nominal voltage of 3/N AC 500/290 V. The frequency range is between 45 and 65 Hz. The device operates without auxiliary voltage, simplifying installation and ensuring independence from additional power sources. Pickup delay is activated, but no time delay is built into this variant.

Compatibility and Accessories
The device is suitable for use in 1- or 3-phase networks. It is available in various housing forms, with the I-housing form (59 mm depth, terminals at bottom) intended for installation and industrial distributors according to DIN 43 880. The S-housing form (98 mm depth, terminals at top) is designed for enclosures with mounting plate and cable duct. The width is 17.5 mm, enabling compact mounting in standard distributors. The device variant IL9171.12 is equipped with neutral conductor connection and adjustable pickup value.

Mounting and Installation
Mounting is done in installation distributors according to DIN 43 880. The connection terminals are located at the bottom, enabling easy wiring. The installation width of 17.5 mm allows integration into standard distributors without additional space requirements. Wiring is done via terminals L1, L2, L3, and N, with terminals L1, L2, and L3 to be bridged for single-phase connection.

Advantages in Operation
The relay provides reliable network monitoring without auxiliary voltage, simplifying installation and maintenance. The LED indicator allows quick visual control of the operating status. The adjustable pickup voltage of 0.55 to 1.05 Un enables flexible adaptation to different network conditions. The hysteresis of approximately 4 % ensures stable switching behavior even with minor voltage fluctuations. The rest current principle ensures that the output relay is not activated in the event of a fault, enabling safe signal transmission. The installation width of 17.5 mm and mounting in standard distributors facilitate integration into existing installations.

Approvals and Markings
The device complies with the standard IEC/EN 60255-1 and carries the CCC approval. Compliance with these standards ensures the reliability and safety of the device in industrial applications.

Enclosure Type
The device is in I-housing form, with a depth of 59 mm and terminals at the bottom, specifically designed for installation and industrial distributors according to DIN 43 880.

Application
The relay is used for monitoring three-phase networks for undervoltage, particularly in installations requiring safety power supply or safety lighting. The application is carried out in accordance with DIN VDE 0100-710 or DIN VDE 0108.

Approvals and Markings
The device complies with the standard IEC/EN 60255-1 and carries the CCC approval. Compliance with these standards ensures the reliability and safety of the device in industrial applications.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/362043
qrcode für Dold 0050823 IL9171.12 undervoltage relay 3/N AC400/230V