Further information for Dold 0050653 BH5928.92/61 AC/DC24V 3-30S emergency stop module
Technical data
1- / 2-channel
1, 2
Approvals
UL
Cat. / PL acc. to EN ISO 13849-1
4/e
Connection
Pluggable screw terminals
Output contacts max.
3 NO contacts, 3 NO contacts delayed
SIL CL acc. to IEC/EN 62061
3
SIL acc. to IEC/EN 62061
3
Thermal current Ith max.
5 A
Width
45 mm
Type
BH 5928
Cross fault detection
Suited as safety gate monitor
Variant
Contact equipping
2 NO contacts, 1 NC contact instantaneous, 3 NO contacts off delay
Nominal voltage
AC/DC 24 V
Time range
3 - 30 s
Approvals and Markings
UL-listed C/US, TÜV, CCC
Variant
With adjustable time delay
The Dold BH5928.92/61 AC/DC24V 3-30S is a safety emergency stop module for use in industrial plants, specifically designed for the protection function of personnel and machinery. It enables the implementation of emergency stop circuits according to Stop Category 1 and is suitable for monitoring sliding safety grilles. The device features an adjustable time delay ranging from 3 to 30 seconds and is designed for operating voltages of AC/DC 24 V. The width is 45 mm, making it suitable for use in standard control panels. The contact configuration includes 2 NO contacts, 1 NC contact immediately, and 3 NO contacts with delayed reset, enabling flexible switching configurations.
Applications
This module is used in safety-critical applications, particularly in the machine and plant construction industry, where a reliable emergency stop function is required. It is used to monitor safety doors and grilles, ensuring that machines can only be started when all safety measures are properly closed. The function as a safety door monitor is explicitly intended, allowing its use in plants with movable safety devices.
Functions and Equipment in Detail
The device offers 1- or 2-channel wiring, enabling flexible integration into different safety architectures. Cross-connection detection is activatable and allows detection of incorrect connections in the emergency stop control circuit, increasing reliability. The status indication for the delayed reset time circuit, as well as LED indicators for power supply, channel 1/2, and time delay, support diagnosis and maintenance. The connection technology uses removable screw terminals suitable for wires with 2 x 1.5 mm² (with ferrule and plastic sleeve DIN 46 228-1/-2/-3/-4) or 2 x 2.5 mm² (with ferrule DIN 46 228-1/-2/-3).
Technology Explained Simply
The time delay of 3 to 30 seconds enables controlled machine shutdown, for example, to complete mechanical movements or ensure personnel are clear of the danger zone. The delayed reset contacts only switch off after the set time has elapsed, which is important for applications requiring delayed shutdown. The thermal rating is defined by a maximum thermal current Ith of 5 A, describing the contact load capacity under continuous operation. The wire break detection at the single-button (connection S33–S34) detects broken or incorrectly routed wires to prevent malfunctions.
Compatibility and Accessories
The module is designed for use in safety control systems meeting the requirements of standards EN ISO 13849-1 and IEC/EN 62061. It complies with Performance Level (PL) e and Category 4 according to EN ISO 13849-1, as well as Safety Integrity Level (SIL) 3 according to IEC/EN 62061. Certifications include UL-listed C/US, TÜV, and CCC, ensuring suitability for various markets. Activation occurs either via a single-button at terminals S33–S34 or via an automatic single-function with a bridge at S13–S14.
Mounting and Installation
Mounting is done in standard control panels with a width of 45 mm. The removable terminal blocks facilitate installation and maintenance. The connection terminals are designed for the specified wire cross-sections, with the use of ferrules and plastic sleeves according to DIN 46 228-1/-2/-3/-4 recommended. Compliance with electrical and mechanical specifications is essential for proper function and safety.
Advantages in Operation
The module offers high safety integrity by complying with SIL 3 and PL e, which is required for critical applications. The integrated status indication and LED indicators enable quick fault diagnosis. Cross-connection detection increases system reliability by identifying incorrect connections. The flexible 1- or 2-channel wiring allows adaptation to different safety architectures. The adjustable time delay provides flexibility in shutdown logic without compromising safety function.