Further information for Dold 0050513 IL9069.12 3/N AC415/240V neutral conductor monitor
Technical data
1- / 3-phase
3
Enclosure design
Distribution board
Measuring range max.
415 V
Output contacts
2 C/O contacts
Standard measuring range
3/N AC 400/230 V
Width
35 mm
Type
IL 9069
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3/N AC 415 / 240 V
Approvals and Markings
CCC
Variant
With fixed response value for asymmetry identification
The Dold IL9069.12 3/N AC415/240V is a neutral conductor monitor of the VARIMETER series, specifically designed for monitoring three-phase networks with a neutral conductor. The device detects disturbances in the network, such as loss of the neutral conductor, interruption in the device supply section, or swapping of the neutral conductor with a phase. It thereby protects connected loads, particularly single-phase devices, from damage due to overvoltage or malfunction caused by undervoltage. Monitoring is performed without auxiliary voltage, simplifying installation and increasing independence from the operating system.
Applications
The neutral conductor monitor is suitable for installations in industrial and installation distributors, particularly in three-phase networks where both three-phase and single-phase loads are connected. It is especially useful for mobile installations connected via plug connections or long supply lines, as voltage drops here can cause asymmetry. The device variant IL9069.12 is designed for standard applications where a fixed detection threshold for asymmetry (maximum 5 %) is sufficient.
Functions and Equipment in Detail
The device monitors the voltages between phases L1, L2, L3 and the neutral conductor N. With correct connection configuration and network asymmetry within the permissible range, a green LED lights up and the output relay remains energized. Upon detection of a fault—such as missing neutral conductor, missing phase, or swapping—the relay drops out and the LED turns off. The response delay is fixed for this variant and is approximately 100 ms. The device operates on the rest current principle, meaning the output relay is de-energized in the event of a fault, rather than being activated.
Technology Explained Simply
The device's power supply is provided via terminals L3-N, with the internal supply voltage requiring at least 0.7 times the rated voltage. The rated voltage is 3/N AC 415/240 V, with the standard measurement range covering 3/N AC 400/230 V. The maximum overload capacity is AC 440 V at all measurement inputs. The frequency range covers 45 to 65 Hz, with the rated frequency being 50/60 Hz. Input currents are approximately 1.5 mA for L1-N and L2-N, and approximately 25 mA for L3-N. The rated power consumption is approximately 6 VA.
Compatibility and Accessories
The device is designed for three-phase networks and can be used regardless of phase sequence. It features two changeover contacts as output contacts, suitable for circuits according to AC 15 (3 A / AC 230 V) and DC 13 (2 A / DC 24 V). The contact materials consist of AgNi 90/10. The thermal current rating is 4 A, and the maximum short-circuit withstand requires a fuse type 4 A gG/gL. The mechanical life expectancy is at least 30 million switching cycles, and the electrical life expectancy is at least 500,000 switching cycles at 1 A and AC 230 V.
Mounting and Installation
The housing design is intended for installation distributors, with a width of 35 mm and a depth of 59 mm. The connection terminals are located at the bottom and are designed for mounting according to DIN 43880. The devices are certified according to IEC/EN 60255-1 and carry the CCC mark. The LED indicator signals the operating status—green illuminated for fault-free network, off in case of fault.
Advantages in Operation
Continuous monitoring of the neutral conductor prevents damage to connected devices and increases operational safety. Simple installation without auxiliary voltage reduces wiring effort. The LED indicator allows for quick visual status check. Use in mobile installations or with long supply lines ensures reliable network monitoring even under difficult conditions. The devices are designed for use in industrial and installation applications, with the IL 9069 housing form specifically designed for distributors according to DIN 43880.