Further information for Dold 0049874 IL9077.12/010 3/N AC415/240V 1-20S under-voltage/over-voltage relay
Technical data
1- / 3-phase
1, 3
Auxiliary voltage
Without
Enclosure design
Distribution board
Measuring range max.
500 V
Output contacts
2 C/O contacts
Standard measuring range
3/N AC 400/230 V
Width
35 mm
Type
IL 9077
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3/N AC 415/240 V
Time delay
0,1 - 20 s
Approvals and Markings
CCC
Variant
With neutral connection. De-energized on trip. With asymmetry detection
The Dold IL9077.12/010 is an undervoltage and overvoltage relay for monitoring AC and three-phase networks, particularly suitable for monitoring self-generation systems in accordance with VDE 0100. The device operates on the zero-current principle and requires no auxiliary voltage, making it especially suitable for use in industrial and installation distributors. It is designed for a rated voltage of 3/N AC 415/240 V and can be used in both single-phase and three-phase systems. The design is as an installation distributor with a width of 35 mm, allowing it to be mounted in standard distributor boxes according to DIN 43880.
Applications
This relay is used for continuous monitoring of voltage fluctuations in electrical networks. It is particularly intended for applications in industry, energy generation systems such as photovoltaic or wind power plants, and buildings with self-supply. The function enables early detection of network faults to prevent damage to connected devices and enhance operational safety.
Functions and Features in Detail
The device features 2 changeover contacts as output contacts, which drop out in the event of a fault. The pickup values for overvoltage (0.9 to 1.3 times rated voltage) and undervoltage (0.7 to 1.1 times rated voltage) are separately adjustable, allowing flexible adaptation to different network conditions. The time delay can be set between 0.1 and 20 seconds to filter out short-term voltage fluctuations and avoid unwanted tripping. In the IL9077.12/010 version, asymmetry detection is integrated, enabling detection of voltage asymmetry exceeding approximately 5 to 10 %, even if all phase voltages are within the permissible range. This allows detection of phase backfeed or other network asymmetries.
Technology Explained Simply
Monitoring is performed by measuring phase voltages against the neutral conductor (N). In devices without an N connection, L1 and L2 are measured against L3. In normal condition, a green LED lights up and the output relay is energized. If the set pickup value for overvoltage is exceeded or the undervoltage threshold is undershot, the relay drops out after the set delay time and the green LED turns off. Two red LEDs then indicate the fault cause: “<U” for undervoltage or “>U” for overvoltage. Upon returning to normal condition, a hysteresis of approximately 4 % of the set value prevents chatter. The LED indication allows quick network fault diagnosis without additional measuring instruments.
Compatibility and Accessories
The device is designed for single- and three-phase networks and can also be used in single-phase installations. The I-type design (59 mm depth, terminals at bottom) is suitable for installation and industrial distributors. The IL9077.12/010 variant includes a neutral conductor connection and asymmetry detection. There are also variants with phase sequence detection (e.g. IL9077/003), but only without N connection. The devices comply with the standard IEC/EN 60255-1 and carry the CCC certification.
Mounting and Installation
Mounting is done in standard distributor boxes with 35 mm width. The terminals are located at the bottom, facilitating integration into installation distributors. The devices are designed for use in installation distributors and require no additional auxiliary voltage. Settings for voltage thresholds and time delay are adjusted via rotary controls on the device.
Operational Advantages
Due to the separate adjustability of overvoltage and undervoltage thresholds, as well as the adjustable time delay, the device can be adapted to different network conditions. The integrated asymmetry detection extends functionality compared to standard monitoring relays. The LED indication enables quick visual fault diagnosis. The zero-current principle and fault tolerance via hysteresis ensure reliable and low-maintenance operation. The devices are designed for use in industrial and installation environments, with the I-type design specifically intended for installation distributors.
Certifications and Markings
The device complies with the standard IEC/EN 60255-1 and carries the CCC certification. The measurement ranges extend up to 500 V, with the standard measurement range being 3/N AC 400/230 V. The devices are designed for use in single- and three-phase networks, with phase sequence being arbitrary.