Further information for Dold 0049448 BH5928.92/61 AC/DC24V 0,3-3S emergency stop module
Technical data
1- / 2-channel
1, 2
Approvals
UL
Cat. / PL acc. to EN ISO 13849-1
4/e
Connection
Pluggable screw terminals
Output contacts max.
3 NO contacts, 3 NO contacts delayed
SIL CL acc. to IEC/EN 62061
3
SIL acc. to IEC/EN 62061
3
Thermal current Ith max.
5 A
Width
45 mm
Type
BH 5928
Cross fault detection
Suited as safety gate monitor
Variant
Contact equipping
2 NO contacts, 1 NC contact instantaneous, 3 NO contacts off delay
Nominal voltage
AC/DC 24 V
Time range
0,3 - 3 s
Approvals and Markings
UL-listed C/US, TÜV, CCC
Variant
With adjustable time delay
The Dold emergency stop module BH5928.92/61 AC/DC24V 0.3-3S is a safety relay for use in industrial plants, particularly for the protection function of personnel and machines. It is designed to implement emergency stop circuits according to Stop Category 1 and enables monitoring of sliding safety guards. The device is designed as a safety module to be integrated into control panels to ensure safety-related functions such as drive disconnection or monitoring of access protection systems. The width is 45 mm, enabling compact mounting in standard control panels.
Applications
This module is intended for use in safety-critical applications, particularly in manufacturing industry, on machines with moving parts, or in plants equipped with safety guards. It is suitable as a safety door monitor to ensure that machines can only be started when all safety guards are correctly closed. The function as an emergency stop control enables immediate disconnection in case of danger, with the reset delay for the contacts adjustable between 0.3 and 3 seconds. This is particularly useful to avoid unintended disconnections while ensuring a safe response in real hazard situations.
Functions and Equipment in Detail
The device features contact configuration with 2 NO contacts, 1 NC contact immediately, and 3 NO contacts with delayed reset. The delayed reset contacts ensure that disconnection does not occur immediately, but after an adjustable delay, which is required in certain applications. The connection technology uses removable screw terminals, enabling flexible and secure connections. The wiring connections can be made with stranded wires up to 2.5 mm² and compatible ferrules according to DIN 46 228-1/-2/-3/-4. The status indicator for the delayed reset timing circuit, as well as LED indicators for power supply, channel 1/2, and time delay, allow visual monitoring of the operating status.
Technology Explained Simply
The module operates with a nominal voltage of AC/DC 24 V and is designed for 1- or 2-channel wiring. Short-circuit detection at the single-button input (connection S33-S34) detects whether a wire break or short circuit is present, increasing the reliability of the safety function. Activation occurs either via the single-button input at S33-S34 or via an automatic start function activated by a bridge at S13-S14. The thermal current rating is maximum 5 A, defining the contact load capacity. The time delay is adjustable and serves to adapt to specific requirements of machine control.
Compatibility and Accessories
The module is designed for use in safety systems complying with the requirements of standards EN ISO 13849-1 and IEC/EN 62061. It meets Performance Level (PL) e and Category 4 according to EN ISO 13849-1, as well as the Safety Integrity Level (SIL CL) 3 according to IEC/EN 62061. Certifications include UL-listed C/US, TÜV, and CCC, enabling use in various markets. It is suitable as a safety door monitor and can be used in systems requiring monitoring of sliding safety guards.
Mounting and Installation
Mounting is carried out in standard control panels with a width of 45 mm. The removable screw terminals facilitate installation and maintenance. The connection terminals are clearly labeled, with connections for the emergency stop function (S33-S34) and the automatic start function (S13-S14) defined. The LED indicators support commissioning and troubleshooting by visually displaying the operating status.
Advantages in Operation
The module offers high safety integrity by complying with SIL 3 and PL e standards, ensuring reliable operation in safety-critical applications. The adjustable time delay allows flexible adaptation to different requirements. Short-circuit detection increases fault tolerance, and LED indicators simplify diagnostics. The use of removable terminals and the compact design support efficient installation and maintenance in industrial environments. Certifications according to UL, TÜV, and CCC enable use in various regions and industries.