Further information for Dold 0049403 undervoltage relay IL9171.12/2003/NAC400/230V0,85UN
Technical data
1- / 3-phase
1, 3
Auxiliary voltage
Without
Enclosure design
Distribution board
Nominal voltage max.
3/N AC 500 / 290 V
Output contacts
2 C/O contacts
Width
17,5 mm
Type
IL 9171
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3/N AC 400 / 230 V
Response value
0,85 Un
Time delay
without
Approvals and Markings
CCC
Variant
With N. NC circuit operation. Without time delay. Fixed response value
The Dold undervoltage relay IL9171.12/2003/NAC400/230V0,85UN is designed for monitoring three-phase power networks for undervoltage and enables automatic switching to a safety power supply or safety lighting in accordance with DIN VDE 0100-710 and DIN VDE 0108. It is designed for use in industrial and installation distributors and operates on the no-current principle, whereby the output relay is not activated in the event of a fault. The device variant is rated for a nominal voltage of 3/N AC 400/230 V and features a fixed pickup value of 0.85 Un. The width is 17.5 mm, and the device is manufactured in I-form, intended for installation and industrial distributors according to DIN 43 880. The connection terminals are located at the bottom, and the depth is 59 mm.
Applications
This relay is used to monitor voltage in three-phase networks and trigger a safe response in the event of undervoltage. It is particularly suitable for applications where automatic switching to an emergency power supply is required in the event of voltage drop or phase loss. The device variant without time delay is suitable for systems requiring an immediate response to fault conditions. Monitoring is independent of phase sequence, allowing flexible installation. In single-phase operation, terminals L1, L2, and L3 must be bridged.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which can be used to control auxiliary circuits or switching operations. The LED indicator displays the status of the output relay: the yellow LED lights up when the relay is activated. Monitoring is performed by measuring the arithmetic mean of each phase against the neutral conductor (N). For variants without neutral conductor connection, L1 and L3 are measured against L2 (IK/SK 9171) or L1 and L2 against L3 (IL/SL 9171). The device variant operates without auxiliary voltage, simplifying installation and increasing reliability.
Technology Explained Simply
The operation is based on continuous measurement of the network voltage. When the voltage drops below the pickup value of 0.85 Un, the fault condition is detected and the output contacts switch accordingly. The no-current principle means that the relay is not activated during normal operation and only responds in the event of a fault. The hysteresis is approximately 4 %, preventing the device from switching uncontrollably due to minor voltage fluctuations. The maximum rated voltage is 3/N AC 500/290 V, and the device is designed for frequencies between 45 and 65 Hz. The overload capacity is 1.15 Un continuously.
Compatibility and Accessories
The relay is suitable for single- and three-phase connections and can be used in 3/N AC 400/230 V networks as well as in other voltage ranges, provided the rated voltage remains within the permissible limits. It is equipped with a neutral conductor connection, enabling use in networks with an N conductor. The device variant without time delay is intended for applications requiring an immediate response. The width of 17.5 mm allows for compact mounting in standard distributor enclosures.
Mounting and Installation
Mounting is performed in installation and industrial distributors according to DIN 43 880. The connection terminals are located at the bottom, and the depth is 59 mm. The device variant is designed for direct mounting in distributor enclosures, with terminals provided for connecting the wires. Installation does not require additional auxiliary voltage, simplifying wiring. The phase sequence is arbitrary, allowing flexible installation.
Advantages in Operation
The relay provides reliable network monitoring without additional auxiliary voltage. The LED indicator allows for quick visual inspection of the operating status. The width of 17.5 mm and I-form ensure compact mounting in standard distributor enclosures. The use of the no-current principle increases safety, as the relay is not activated in the event of a fault. The hysteresis of approximately 4 % prevents unwanted switching operations due to minor voltage fluctuations. The device variant is rated for a nominal voltage of 3/N AC 400/230 V and can be used in various industrial and installation applications.