Dold 0049306, EAN: 4030641493066

Dold 0049306 IL9277.12 AC220-240V 0,1-15A under-overcurrent relay

Dold 0049306 IL9277.12 AC220-240V 0,1-15A under-overcurrent relay

Lieske Part No. 1002372
Mfg Part No 0049306
EAN-Code 4030641493066
Manufacturer Dold
Here only 276,53 EUR
329,07 EUR incl. VAT

Further information for Dold 0049306 IL9277.12 AC220-240V 0,1-15A under-overcurrent relay

Technical data
1- / 3-phase1
Enclosure designDistribution board
Output contacts2 C/O contacts
Width35 mm
TypeIL 9277
Operate delayYes
Variant
Auxiliary voltageAC 220 - 240 V
Contact equipping2 changeover contacts
Measuring range0,1 - 15 A
Switching delay0,1 - 20 s
Approvals and MarkingsCCC
VariantSingle phase current relay. De-energized on trip
The Dold IL9277.12 is a single-phase current relay of the VARIMETER series, designed for monitoring currents in AC and three-phase networks. It is used for detecting overcurrent and undercurrent and responds with an adjustable time delay when the set switching point is exceeded or undershot. The device operates on the zero-current principle, whereby the output relay is not activated in the event of a fault, ensuring safe disconnection during malfunctions. The auxiliary voltage is AC 220–240 V, and the measurement ranges are between 0.1 and 15 A. The switching delay is adjustable from 0.1 to 20 seconds to account for or filter short-term current surges.

Applications
This relay is intended for use in industrial and railway applications where reliable current monitoring is required. It is particularly suitable for installations where operation during current drop or excess is critical, such as in production plants, pump controls, or motor monitoring. The galvanic isolation between the auxiliary circuit and the measurement circuit increases safety and prevents interference in the control circuit.

Functions and Features in Detail
The device features 2 changeover contacts as output contacts, which can be used to control auxiliary devices or alarms. The hysteresis is fixed at approximately 4 % to avoid switching operations due to minor fluctuations. Operational readiness as well as overcurrent and undercurrent conditions are indicated by LED displays: a green LED indicates normal operation, a red LED indicates overcurrent (I max), and another red LED indicates undercurrent (I min).

Technical Explanation
The IL9277.12 integrates a current transformer with measurement ranges from 0.5 to 100 A, although the display and control are limited to 0.1 to 15 A. Measurement is performed via terminals i and k, while the auxiliary voltage is supplied via A1 and A2. The measurement range selection is done via jumpers on terminals Z1 to Z4. The switching delay allows differentiation between short-term disturbances and permanent faults, thus avoiding false tripping. The device complies with the standard IEC/EN 60255-1, which defines requirements for electrical measuring instruments and relays.

Compatibility and Accessories
The relay is designed for use in installation and industrial distributors according to DIN 43880. It is supplied in I form with a mounting depth of 61 mm and terminals located at the bottom, making it suitable for mounting in standard distributors. The mounting width is 35 mm, and installation is done either on a DIN rail or by screws. It is compatible with other devices in the VARIMETER series, particularly models SL 9277 and SP 9277, which offer different housing forms and configurations.

Mounting and Installation
Installation is carried out in an installation distributor, with terminals for current measurement (i, k) and auxiliary voltage (A1, A2) connected according to the wiring diagrams. The terminals are located at the bottom, enabling easy integration into existing control systems. Mounting is done via DIN rail or screws, with the mounting depth of 61 mm sufficient to fit the device into standard distributors.

Operational Advantages
Thanks to adjustable thresholds and switching delay, the relay can be flexibly adapted to various applications. The LED indicators allow for quick visual inspection of the operating status. Galvanic isolation between the measurement and auxiliary circuits increases safety and prevents interference. The zero-current principle ensures that the relay is not activated in the event of a fault, providing safe disconnection. Compliance with the standard IEC/EN 60255-1 ensures reliability and interoperability in industrial installations.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1002372
qrcode für Dold 0049306 IL9277.12 AC220-240V 0,1-15A under-overcurrent relay