Further information for Dold 0049014 BH5928.93/61 DC24V 1-10S emergency stop module
Technical data
1- / 2-channel
1, 2
Approvals
UL
Cat. / PL acc. to EN ISO 13849-1
4/e
Connection
Pluggable screw terminals
Output contacts max.
3 NO contacts, 3 NO contacts delayed
SIL CL acc. to IEC/EN 62061
3
SIL acc. to IEC/EN 62061
3
Thermal current Ith max.
5 A
Width
45 mm
Type
BH 5928
Cross fault detection
Suited as safety gate monitor
Variant
Contact equipping
3 NO contacts, 3 NO contacts off delay
Nominal voltage
DC 24 V
Time range
1 - 10 s
Approvals and Markings
UL-listed C/US, TÜV, CCC
Variant
With adjustable time delay
The Dold emergency stop module type BH5928.93/61 DC24V 1-10S is a safety-relevant switching component for use in industrial plants. It is designed for the safe disconnection of machines and systems in emergency situations, particularly in combination with safety doors or sliding safety grilles. The device is designed for implementing Stop Category 1 according to EN ISO 13849-1 and offers an adjustable time delay in the range of 1 to 10 seconds. The width is 45 mm, making it suitable for standard control panels. The nominal voltage is DC 24 V, and the module is equipped with removable screw terminals, enabling flexible wiring.
Applications
The module is used in safety-critical applications, particularly for monitoring safety doors and sliding safety grilles. It is suitable as a safety door monitor and can be integrated into emergency stop circuits to ensure the safety of personnel and machinery. The functions are designed for use in industrial environments where reliable and rapid response in case of failure is required.
Functions and Equipment in Detail
The device features contact configuration with up to 3 normally open (NO) contacts as immediate contacts and 3 normally open contacts as delayed return contacts. The time delay is adjustable and serves controlled disconnection, for example, to safely bring machines into a standstill state. The status indication for the delayed return timing circuit enables visual monitoring of the operating state. LED indicators signal the power connection, the status of channels 1 and 2, and the active time delay. Cross-connection detection is activatable and serves to detect incorrect connections in the control circuit.
Technology Explained Simply
The safety functions of the module are based on standards EN ISO 13849-1 and IEC/EN 62061. It achieves Performance Level (PL) e and Category 4 according to EN ISO 13849-1, indicating high safety performance for critical applications. The Safety Integrity Level (SIL) claim limit (SIL CL) 3 according to IEC/EN 62061, as well as assignment to SIL 3 according to IEC/EN 61508 and IEC/EN 61511, underline its suitability for safety-critical systems. The thermal current Ith max. is 5 A, defining the maximum load capacity of the contacts. The connection technology with removable screw terminals enables easy installation and maintenance. The wire connections can be made with stranded wires up to 2.5 mm² and ferrules according to DIN 46 228-1/-2/-3/-4.
Compatibility and Accessories
The module is suitable for single- or dual-channel wiring and can be activated optionally via a single-button switch at terminals S33-S34 or via an automatic single-function with a bridge at S13-S14. Cross-connection detection can be configured via the terminals. It is certified with UL-listed C/US, TÜV, and CCC, confirming compliance with international safety standards.
Mounting and Installation
Mounting is carried out in standard control panels with a width of 45 mm. The removable terminal blocks facilitate installation and maintenance. The connection terminals are clearly labeled to ensure error-free wiring. The wire connection detection at the single-button switch ensures safe detection of incorrect connections.
Advantages in Operation
The module provides high safety performance through the combination of immediate and delayed contacts. The adjustable time delay enables adapted disconnection, increasing operational safety. The LED indicators and the status indication for the timing circuit facilitate diagnosis and maintenance. The certifications according to UL, TÜV, and CCC ensure compliance with international safety requirements. The construction with removable terminals and the clear layout of connections reduce the risk of errors during installation and maintenance.