Dold 0048872, EAN: 4030641488727

Dold 0048872 undervoltage relay AC230V 0,55-1,05UN4%

Dold 0048872 undervoltage relay AC230V 0,55-1,05UN4%

Lieske Part No. 1153826
Mfg Part No 0048872
EAN-Code 4030641488727
Manufacturer Dold
Here only 118,63 EUR
141,17 EUR incl. VAT

Further information for Dold 0048872 undervoltage relay AC230V 0,55-1,05UN4%

Technical data
1- / 3-phase1
Auxiliary voltageWithout
Enclosure designDistribution board
Nominal voltage max.AC 230 V, DC 125 V
Output contacts1 C/O contact
Width17,5 mm
TypeIK 9173
Operate delayYes
Variant
Contact equipping1 changeover contact
Nominal voltageAC 230 V
Response value0,55 - 1,05 Un 4%
Time delay0,5 - 20 s
VariantNC circuit operation. Settable time delay t1. Settable response value
The Dold undervoltage relay type IK9173.11/030 AC230V 0,55-1,05UN4% is a single-phase voltage monitoring device for industrial applications. It is designed for continuous monitoring of AC power networks for undervoltage conditions and enables early detection of voltage drops to prevent operational disruptions and damage to connected devices. The device operates on the rest current principle, whereby the output relay is not activated in the event of a fault, ensuring safe and reliable signal transmission. The nominal voltage is AC 230 V, and the relay is designed for use in installation and industrial distributors in accordance with DIN 43880. The width of 17.5 mm allows for compact mounting in standard distributor enclosures.

Applications
This relay is suitable for monitoring power networks in industrial plants, railway applications, and systems with unstable voltage supplies. It can be used for automatic switching to a safety power supply or safety lighting in accordance with DIN VDE 0100-710 or DIN VDE 0108. It is particularly advantageous for use in networks with local power generation or in regions with unreliable supply, where certain consumer groups should be switched off with a time delay during voltage dips and re-energized after a defined waiting period. It is also suitable for consumers that must not be re-energized immediately after a short power failure—for example, compressors or certain processing machines.

Functions and Equipment in Detail
The device features an adjustable time delay t1 in the range of 0.5 to 20 seconds, which is only effective as long as the phase voltage L-N is at least 0.5 times the nominal voltage. The pickup value is adjustable within the range of 0.55 to 1.05 times the nominal voltage, with a hysteresis of approximately 4% ensured. Measurement is performed via the arithmetic mean of the voltage between line and neutral conductor (L-N). The output contacts consist of a changeover contact (11-12-14), with the contact material being silver-nickel (AgNi). A yellow LED indicates the state of the output relay: it lights up when contact 11-14 is closed.

Technology Explained Simply
The relay detects an undervoltage condition as soon as the measured voltage falls below the set pickup value. Upon reaching the pickup value, the time delay t1 is activated, enabling a delayed response to ignore short-term voltage dips. The response time of the measuring input during phase failure is approximately 100 ms. The rated operating voltage of the contacts is AC 250 V, and the thermal current Ith is 4 A. The switching capacity according to AC 15 is 3 A for the make contact and 1 A for the break contact at AC 230 V.

Compatibility and Accessories
The relay is designed for use in single-phase networks and complies with the standard IEC/EN 60255-1. It is available in two housing forms: IK 9173 with a depth of 59 mm and bottom-mounted connection terminals for installation distributors, and SK 9173 with a depth of 98 mm and top-mounted terminals for enclosures with a mounting plate. The electrical service life is at least 300,000 switching operations at AC 230 V and 1 A (cos ϕ = 0.5), and the mechanical service life is at least 30 million switching operations. The maximum short-circuit withstand requires a fuse with 4 A gG/gL.

Mounting and Installation
Mounting is carried out in standard installation distributors in accordance with DIN 43880. The connection terminals are arranged at the bottom, enabling easy wiring. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is from -25 °C to +60 °C. The relative humidity is up to 93% at 40 °C, and the maximum altitude is 2000 m. The devices are designed for continuous operation.

Advantages in Operation
Through early detection of voltage drops and the option of time delay, the device can contribute to preventive maintenance and avoid costly damage. The high availability and operational reliability of the system are ensured by reliable signal transmission and simple installation. The use without auxiliary voltage reduces wiring effort and installation complexity. The adjustable parameters allow flexible adaptation to different requirements in industrial applications.