Dold 0048730, EAN: 4030641487300

Dold 0048730 IL9069.12 3/N AC400/230V neutral conductor monitor

Dold 0048730 IL9069.12 3/N AC400/230V neutral conductor monitor

Lieske Part No. 1001934
Mfg Part No 0048730
EAN-Code 4030641487300
Manufacturer Dold
Here only 253,15 EUR
301,25 EUR incl. VAT

Further information for Dold 0048730 IL9069.12 3/N AC400/230V neutral conductor monitor

Technical data
1- / 3-phase3
Enclosure designDistribution board
Measuring range max.415 V
Output contacts2 C/O contacts
Standard measuring range3/N AC 400/230 V
Width35 mm
TypeIL 9069
Operate delayYes
Variant
Contact equipping2 changeover contacts
Nominal voltage3/N AC 400 / 230 V
Approvals and MarkingsCCC
VariantWith fixed response value for asymmetry identification
The Dold IL9069.12 3/N AC400/230V is an N-conductor monitor of the VARIMETER series, specifically developed for monitoring the neutral conductor in three-phase networks. The device detects faults such as missing neutral conductor, neutral conductor break in the device supply line, or swapping of the neutral conductor with a phase. It thereby protects electrical installations and connected loads from damage caused by asymmetric voltage conditions, which can lead to overvoltage or undervoltage, particularly with single-phase loads. The function operates without auxiliary voltage, simplifying installation and reducing wiring effort.

Applications

The N-conductor monitor is designed for use in three-phase networks with 3/N AC 400/230 V and is particularly suitable for installations where single-phase loads are connected to the neutral conductor. It is suitable for installation and industrial distributors, as well as for portable installations connected via plug connections or long supply lines. In such cases, voltage asymmetry may occur due to voltage drops during normal operation, which can be detected and reported by the monitoring function.

Functions and Equipment in Detail

The device detects a missing neutral conductor, interruption of the neutral conductor in the supply line, or swapping of the neutral conductor with a phase. Detection is achieved by measuring the voltages between phases L1, L2, L3 and the neutral conductor N. With correct connection configuration and network asymmetry within the permissible range, a green LED lights up and the output relay is energized. Upon detection of a fault, the relay de-energizes and the LED turns off. The IL9069.12 variant features a fixed threshold for asymmetry detection, which is maximum 5 %. The response delay is activated and amounts to approximately 100 ms.

Technology Explained Simply

The operation is based on the rest current principle, where the output relay is de-energized in the event of a fault, rather than being energized. The device is powered via terminals L3-N, with the internal supply voltage needing to be at least 0.7 times the rated voltage to ensure reliable function. The LED indicator signals the good condition of the network and the position of the output contacts. Phase sequence is arbitrary, allowing flexible installation. The measurement range limits are between 0.7 and 1.1 times the rated voltage, with maximum overload capacity at AC 440 V.

Compatibility and Accessories

The device is designed for three-phase networks with 3/N AC 400/230 V and complies with standard IEC/EN 60255-1. It is manufactured in the IL 9069 form factor, which has a mounting width of 35 mm and a mounting depth of 59 mm. The connection terminals are located at the bottom and are designed for installation and industrial distributors according to DIN 43880. The output contacts consist of two changeover contacts with contact material AgNi 90/10. The rated voltage of the output contacts is AC 250 V, and the thermal current rating is 4 A. The switching capacity is 3 A/AC 230 V (AC 15) and 2 A/DC 24 V (DC 13). The electrical life expectancy is at least 500,000 switching cycles at 1 A/AC 230 V, and the mechanical life expectancy is at least 30 million switching cycles.

Mounting and Installation

Mounting is carried out in installation and industrial distributors according to DIN 43880. The mounting width of 35 mm allows installation in standard distributors. The connection terminals are arranged at the bottom, ensuring easy wiring. Power supply is via terminals L3-N, with the voltage needing to be at least 0.7 times the rated voltage to ensure reliable function. The terminal markings are L1, L2, L3, N for inputs and 11, 12, 14 as well as 21, 22, 24 for the output relays.

Advantages in Operation

The N-conductor monitor provides reliable monitoring of the neutral conductor and protects the installation from damage caused by asymmetric voltages. The LED indicator allows for quick visual inspection of the operating status. The function without auxiliary voltage reduces installation effort. Detection of faults such as neutral conductor break or swapping prevents costly damage to connected devices. The response delay of approximately 100 ms ensures stable reaction without false alarms during short-term voltage fluctuations. The CCC certification and compliance with IEC/EN 60255-1 ensure adherence to international standards.