Dold 0047645, EAN: 4030641476458

Dold 0047645 undervoltage relay IK9173.11/240 AC220V 0,75UN4% 5-15M

Dold 0047645 undervoltage relay IK9173.11/240 AC220V 0,75UN4% 5-15M

Lieske Part No. 1153819
Mfg Part No 0047645
EAN-Code 4030641476458
Manufacturer Dold
Here only 100,11 EUR
119,13 EUR incl. VAT

Further information for Dold 0047645 undervoltage relay IK9173.11/240 AC220V 0,75UN4% 5-15M

Technical data
1- / 3-phase1
Auxiliary voltageWithout
Enclosure designDistribution board
Nominal voltage max.AC 230 V, DC 125 V
Output contacts1 C/O contact
Width17,5 mm
TypeIK 9173
Operate delayYes
Variant
Contact equipping1 changeover contact
Nominal voltageAC 220 V
Response value0,75 Un 4%
Time delay5 - 15 min
VariantNC circuit operation. Settable time delay t2. Fixed response value
The Dold undervoltage relay type IK9173.11/240 AC220V 0,75UN4% 5-15M is a single-phase voltage monitoring device from the VARIMETER series, designed for detecting undervoltages in AC networks. It monitors the network voltage between line and neutral conductor (L-N) and responds when the voltage drops below a predefined pickup value. The device is designed for use in installation and industrial distributors according to DIN 43880 and features a width of 17.5 mm. The nominal voltage is AC 220 V, with a maximum nominal voltage up to AC 230 V. The relay operates on the rest current principle, whereby the output relay is not activated in the event of a fault, ensuring safe and reliable operation.

Applications
This relay is suitable for applications in industrial plants, railway applications, and systems with unstable power grids, for example, in local power generation or in power networks of the 2nd and 3rd world. It enables early detection of impending failures and allows preventive maintenance measures to avoid costly damage. A typical application is automatic switching to a safety power supply or safety lighting according to DIN VDE 0100-710 or DIN VDE 0108 in case of phase failure. The time delay t2 allows consumer groups to be switched back on in stages after a power failure, ensuring network stability.

Functions and Equipment in Detail
The device features an adjustable time delay range of 5 to 15 minutes for re-energizing in the normal state (t2). The pickup value is fixed at 0.75 times nominal voltage (Un) with a hysteresis of 4%. Measurement is performed via the arithmetic mean of the L-N voltage. The output contacts consist of a changeover contact (11-12, 11-14) made of silver-nickel (AgNi). The rated operational voltage is AC 250 V, and the thermal current Ith is specified as 4 A. The switching capacity according to AC 15 is 3 A for closing contacts and 1 A for opening contacts at AC 230 V. The electrical life is at least 300,000 switching operations at AC 230 V and 1 A (cos ϕ = 0.5), and the mechanical life is at least 30 million switching operations.

Technology Explained Simply
The relay detects an undervoltage when the measured voltage falls below 0.75 times the nominal voltage. The time delay t2 ensures that the output relay is only reactivated after a defined waiting period (5–15 min), which is particularly important for unstable networks or for consumers such as compressors that must not be switched back on immediately after a short power failure. The LED indicator signals the state of the output relay: when the contact (11-14) is closed, a yellow LED lights up. The response time of the measuring input in case of phase failure is approximately 100 ms.

Compatibility and Accessories
The relay is designed for use in installation distributors with bottom-mounted connection terminals and corresponds to form IK 9173. It is certified according to IEC/EN 60255-1. The maximum overload capacity is 1.15 times nominal voltage continuously. The frequency range is between 45 and 65 Hz. The operating temperature ranges from -20 °C to +60 °C, and the storage temperature ranges from -25 °C to +60 °C. The maximum permissible air humidity is 93% at 40 °C, and the altitude is limited to ≤ 2000 m. The short-circuit withstand requires a maximum fuse rating of 4 A gG/gL.

Mounting and Installation
The device is mounted in installation and industrial distributors according to DIN 43880. The connection terminals are located at the bottom, the width is 17.5 mm, and the depth is 59 mm. Mounting is performed in standard distributor enclosures, with terminals for voltage supply (L, N) and output contacts (11, 12, 14) clearly labeled. Installation does not require additional auxiliary voltage, simplifying wiring.

Advantages in Operation
Early detection of undervoltages enables preventive maintenance and increases operational safety and availability of the system. The adjustable time delay t2 protects sensitive consumers from uncontrolled re-energizing. The LED indicator provides visual feedback on the relay’s status. The high mechanical and electrical life ensures long service life. The device is designed for continuous operation and complies with standards for industrial applications.